background image

SuperiorFireplaces.us.com

126700-01C

11

INSTALLATION

Continued

Figure 7 - Minimum Mantel Clearances 

for Built-In Installation

Supplied

Firebox Hood

Must Be Used

at All Times

Wire-mesh

Screen

Firebox

Noncombustible

Material May

Project Off this

Surface above

the Firebox Hood

Mantel Shelf

Note: Any portion of the

mantel shelf must NOT

extend beyond this profile.

12" 16" 20"

1

/

2

"

3

/

4

"

12"

Note: All vertical

measurements are

from top of fireplace

hood opening to

bottom of mantel shelf.

These minimum

clearances replace any

other recommended

clearances supplied

with your ANSI Z21.11.2

approved gas logs.

Wall board or facing

material (above

firebox) may be of

combustible material,

including decorative

mantel ornaments or

other similar projec-

tions off of the facing

material.

Framing

Material

Figure 6 - Minimum Clearance for 

Combustible to Wall

*Minimum 16" from Side Wall 

Example

*

WARNING: Maintain the 

minimum clearances. If you can, 

provide greater clearances from 

floor, ceiling and adjoining wall.

INSTALLATION CLEARANCES

Carefully follow the instructions below. This 

will ensure safe installation.

Minimum Wall and Ceiling Clearances 

(see Figure 6)

A.  Clearances from the side of the fireplace 

cabinet to any combustible material and 

wall should follow diagram in 

Figure 6

.

 

Example

:

 The face of a mantel, bookshelf, 

etc. is made of combustible material and 

protrudes 3-1/2" from the wall. This com

-

bustible material must be 4" from the side 

of the fireplace cabinet 

(see 

Figure 4

)

.

B.  Clearances  from  the  top  of  the  firebox 

opening to the ceiling should not be less 

than 42".

C.  When firebox is installed on carpeting, tile 

(other than ceramic) or other combustible 

material,  other  than  wood  flooring,  the 

firebox should be installed on a metal or 

wood panel extending the full width and 

depth of the enclosure.

D.  Clearances from the bottom of firebox to 

the floor is 0".

These  fireboxes  can  be  installed  as  free

-

standing units against a wall with approved 

cabinet mantels that may be available from 

your retailer or supplier, or as a built-in unit. 

The clearances are the same for either instal-

lation method.

 CAUTION: Do not allow the 

vent-free gas log appliance to 

touch or extend beyond the 

firebox screen.

NOTICE: Surface temperatures 

of adjacent walls and mantels be-

come hot during operation. Walls 

and mantels above the firebox 

may become hot to the touch. 

If installed properly, these tem-

peratures meet the requirement 

of the national product standard. 

Follow all minimum clearances 

shown in this manual.

Mantel Clearances for Built-In 

Installation

If placing custom mantel above built-in fire

-

box, you must meet the minimum allowable 

clearance between mantel shelf and top of 

firebox  opening  shown  in 

Figure 7

. These 

are the minimum allowable mantel clearances 

for a safe installation. Use larger clearances 

wherever possible to minimize the heating of 

objects and materials placed on the mantel.

Maintain adequate clearances for accessibility for purposes 

of servicing and proper operation.

Minimum clearance requirements include any projections such 

as shelves, window sills, mantels, etc. above the appliance.

Содержание VRT4536WH

Страница 1: ...ury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appli...

Страница 2: ...ANSI Z21 11 2 decorative type un vented room heater WARNING Anychangetothisfire box or its controls can be dangerous DANGER Carbon monoxide poi soning may lead to death WARNING Do not use a blower ins...

Страница 3: ...te clearances around air openings 11 Use only the provided hood See Parts Page 19 Due to high temperatures the ap pliance should be located out of traffic and away from furniture and draperies Do not...

Страница 4: ...Fuel Gas Code ANSI Z223 1 NFPA 54 National Fuel Gas Code latest edition Firebox must be electrically grounded in accordance with the National Electrical Code ANSI NFPA 70 latest edition COMMONWEALTH...

Страница 5: ...T SPECIFICATIONS 36 MODELS Figure 1 36 Models VRT4536WS and VRT4536WH Picture may vary from actual fireplace 30 1 2 29 30 11 1 8 54 3 4 7 7 8 7 36 45 1 4 33 8 91 2 50 1 8 363 8 7 3 8 111 8 3 3 4 4 7 8...

Страница 6: ...FICATIONS Continued 42 MODELS Figure 2 42 Models VRT4542WS and VRT4542WH Picture may vary from actual fireplace 4 7 8 54 3 4 7 7 8 7 36 3 8 50 1 8 42 51 1 4 32 3 8 3 3 4 30 3 8 8 3 4 13 3 3 8 9 1 2 30...

Страница 7: ...CIFICATIONS Continued 50 MODELS Figure 3 50 Models VRT4550WS and VRT4550WH Picture may vary from actual fireplace 363 8 50 1 8 8 3 4 13 33 8 91 2 59 1 4 50 7 7 8 7 30 54 3 4 11 1 8 32 3 8 3 3 4 38 3 8...

Страница 8: ...termine if the space is confined or unconfined Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them DETERMINING FRESH AIR FLOW FOR HEATER LOCATIO...

Страница 9: ...u Hr the space can support with the actual amount of Btu Hr used ________ Btu Hr maximum the space can support ________ Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr maximum the space can...

Страница 10: ...d ser vice person must install firebox Follow all local codes CAUTION Log heaters in stalled in this firebox create warmaircurrents Thesecurrents move heat to wall surfaces next to firebox Installing...

Страница 11: ...eplace cabinet see Figure 4 B Clearances from the top of the firebox opening to the ceiling should not be less than 42 C When firebox is installed on carpeting tile other than ceramic or other combust...

Страница 12: ...s in Figure 9 for rough opening 2 Install gas piping to firebox location See Gas Line Installation on Page 16 and Con necting to Gas Supply in log set owner s manual WARNING Do not allow any combustib...

Страница 13: ...t mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be avail able from your retailer or custom built for your home 1 Assemble cabinet...

Страница 14: ...NEL PANEL RIGHT BRICK REAR BRICK PANEL BOTTOM BRICK PANEL ASH PANEL UPPER CORNER BRACKET 2x 3 Install rear refractory panel This panel has a top and bottom To determine which is which match up the pat...

Страница 15: ...of fireplace and pull out insula tion from gas line conduit sleeve Save insulation for reuse Replace screws 3 Run a 1 2 black iron gas line into fireplace through the rear at gas line conduit sleeve...

Страница 16: ...If you wish to install an unvented vent free gas log set only unvented gas log sets which have been found to comply with the standard for unvented room heaters ANSI Z21 11 2 are to be installed in thi...

Страница 17: ...Outside Air Kit Collar Hood 3 Flex for Floor Venting Cat No F1094 Model AK4B 50 piece Bulk Outside Air Kit Collar Only Kit OPTIONAL OUTSIDE AIR KIT FOR SIDEWALL INSTALLATION Cat No F1091 Model AK4 4 A...

Страница 18: ...10 11 13 14 15 16 14 3 22 20 21 20 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 Cat No Model Interior F0277 VRT4536WS White Stack F0278 VRT4536WH White Herr F0279 VRT4542WS White Stack F0280 VRT4542...

Страница 19: ...irebox Top 1 20 J4342 Screen 36 2 J4341 Screen 42 2 J4340 Screen 50 2 F3235 Screen 36 Stainless 2 F3236 Screen 42 Stainless 2 F3237 Screen 50 Stainless 2 21 J6928 Screen Rod 36 2 J4391 Screen Rod 42 2...

Страница 20: ...vary from actual 1 2 5 3 4 6 6 1 2 3 4 5 6 7 7 WARNING REFRACTORY PANELS LIFTING HAZARD SINGLE PERSON LIFT COULD CAUSE INJURY USE ASSISTANCE WHEN MOVING OR LIFTING IMPORTANT Installation of refractor...

Страница 21: ...tural White 1 Right Stacked 42 Natural White 1 Right Herringbone 42 Natural White 1 Right Stacked 50 Natural White 1 Right Herringbone 50 Natural White 1 4 Left Stacked 36 Natural White 1 Left Herring...

Страница 22: ..._________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________________...

Страница 23: ...ural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c d...

Страница 24: ...istributor for fireplace code information Printed in U S A 2021 Innovative Hearth Products P N 126700 01 Rev C 06 2021 1769 East Lawrence Street Russellville AL 35654 SuperiorFireplaces us com Record...

Отзывы: