background image

SuperiorFireplaces.us.com

900991-00A

6

AIR FOR COMBUSTION AND VENTILATION  

Continued

4.  Compare the maximum Btu/Hr the space can support with the 

actual amount of Btu/Hr used.

   ________ Btu/Hr (maximum the space can support)
   ________ Btu/Hr (actual amount of Btu/Hr used)
  Example: 63,360 Btu/Hr (maximum the space can support) 

   

79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual 

Btu/Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:

A.

  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation 

Air From Inside Building, 

Page 6

.

B.

  Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.

 Install a lower Btu/Hr heater, if lower Btu/Hr size makes room 

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no ad-

ditional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 

combustion air, combustion and ventilation air shall 

be provided by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, the In-

ternational Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building 

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 12" 

of the floor on the wall connecting the two spaces 

(see options 1 and 

2, 

Figure 2

). 

You can also remove door into adjoining room 

(see option 

3, 

Figure 2

). 

Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, Air for Combustion and Ventilation for required size of ventilation 

grills or ducts.

Figure 3 - Ventilation Air from Outdoors

Figure 2 - Ventilation Air from Inside Building

Or 

Remove 

Door into 

Adjoining 

Room, 

Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation 

Grills  

Into Adjoining  

Room, 

Option 1 

12" 

12" 

Outlet 

Air 

Ventilated 

Attic  

Outlet 

Air 

Inlet 

Air 

Inlet Air 

Ventilated  

Crawl Space 

To 

Crawl

Space

To Attic 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and 

one within 12" of the floor. Connect these items directly to the out-

doors or spaces open to the outdoors. These spaces include attics 

and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

Содержание F4106

Страница 1: ...tions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier INSTALLER Leave this manual...

Страница 2: ...ow directly into the firebox Avoid any drafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting WARNING Do not...

Страница 3: ...est 43rd Street 4th floor New York NY 10036 National Fire Protection Association Inc 1 Batterymarch Park Quincy MA 02169 7471 SAFETY Continued PRODUCT FEATURES OPERATION This firebox has been tested a...

Страница 4: ...15 7 8 403 7 1 2 190 12 305 1 3 8 35 5 1 2 140 34 3 8 873 VRE4242 Series 42 1067 28 711 47 3 4 1213 41 1 4 1048 29 1 2 749 20 508 3 76 8 3 8 213 15 7 8 403 7 1 2 190 12 305 1 3 8 35 5 1 2 140 34 3 8 8...

Страница 5: ...s between wall panels at penetrations for plumbing electrical and gas lines and at other openings If your home meets all three criteria above you must provide additional fresh air See Ventilation Air...

Страница 6: ...ternational Fuel Gas Code or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining u...

Страница 7: ...instructions This will ensure safe installation Minimum Wall and Ceiling Clearances see Figure 4 A Clearances from side of fireplace cabinet to any combustible material and wall should follow diagram...

Страница 8: ...llyinsertfireboxintoroughopening 5 Attach firebox to wall studs using nails or wood screws through holes in nailing flange see Figure 5 6 Install and properly test gas log heater Follow installation i...

Страница 9: ...ptional Drain Pan Corner Installation A C D H F G E Back Wall Of Chase Enclosure Including Finishing Materials If Any Rough Framing Face Unfinished Shown C G A Parallel Installation Rough Framing Face...

Страница 10: ...hisel rough edges of hole you have made to smooth edges This hole will line up with hole in outer casing CAUTION Donotuseexcessiveforcetoremovethe knockout Too much force may damage the firebrick conc...

Страница 11: ...ound the bottom of the drain pan before positioning the fireplace on its location Figure 7a Step 2 On the exposed drain hole install a PVC threaded coupling reducer 3 4 x 1 2 going from the top of the...

Страница 12: ...so visit our web site at SuperiorFireplaces us com Figure 8 TYPICAL INSTALLATION INSTALLING FIREPLACE HOOD These brushed stainless hood trim kits 36 hood kit Catalog no F4128 and 42 hood kit Catalog n...

Страница 13: ...ractory panels a new look Kit includes foam roller roller handle paint tray and one can of stain Available stain colors are Creamer ivory Rust terra cotta and Cappuccino rosy taupe Creamer Rust Cappuc...

Страница 14: ...Stacked F4107 VRE4236WH OD VF Firebox 36 White Herringbone F4108 VRE4242WS OD VF Firebox 42 White Stacked F4109 VRE4242WH OD VF Firebox 42 White Herringbone WARNING Never use substitute materials Use...

Страница 15: ...diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury AVERTISSEMENT Risque de dommages ou de blessures si les pi ces ne sont...

Страница 16: ...1 6 3 4 5 3b 3a 3c 3d No Description VRE4236WS White Stacked VRE4236WS White Herringbone VRE4242WS White Stacked VRE4242WH White Herringbone Part No Qty Part No Qty Part No Qty Part No Qty 3 Refracto...

Страница 17: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 18: ...cts Consult your local distributor for fireplace code information Printed in U S A 2019 Innovative Hearth Products P N 900991 00 Rev A 06 2019 1769 East Lawrence Street Russellville AL 35654 SuperiorF...

Отзывы: