Installation 

900684-01 06/2018

Innovative Hearth Products
DRT3000 Series Direct-Vent Gas Fireplaces

22

8. 

Place the Fireplace in the Framing and Secure

NOTE: 

Nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are 

EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper.

NOTE: 

Combustible framing may be in direct contact with the nailing flanges and may be located within 1/2” of screw 

heads and the firebox wrapper in areas adjacent to the nailing flanges.
Frame the opening to the exact dimensions specified in the framing details in this manual.

1. 

Bend out the appropriate nailing flanges for the drywall / finish material to be used (

Figure 11

). Nailing flanges 

are provided for:
•  flush framing,
•  1/2”, and
•  5/8” framing depths.

2. 

Secure the fireplace to the side framing members using the unit’s nailing flanges—one top and bottom on each 

side of the fireplace front (

Figure 11

). Use 8d nails or the equivalent.

Figure 11 - Nailing Flanges

Side 

framing

Unit nailing flange

(no clearance to combustible 

framing is required)

VENT SYSTEM PREPARATION

9. 

Select a Horizontal or Vertical Vent System

1. 

With the fireplace secured in the framing, determine the vent route and identify the exterior termination location. 

The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Use only approved 

vent components 

(

Page 8

 and 

Pages 47-48

)

.

NOTE: 

This fireplace must be vented directly to the outside.

 WARNING 

The vent system may not service multiple appliances, and must never be connected to a 

flue serving a separate solid fuel burning appliance.

NOTE: 

The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for 

inspection openings in the enclosing wall at any of the joints in the vent pipe.

Содержание DRT3000 Series

Страница 1: ...e le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou par le fournisseur de gaz INSTALLER Leave...

Страница 2: ...VITRE EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas...

Страница 3: ...oca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio...

Страница 4: ...13 Minimum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 Construct the Fireplace Framing 17 Prepare the Fireplace T...

Страница 5: ...t subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou u...

Страница 6: ...Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoni...

Страница 7: ...combinations of fuels will degrade the performance of this system and may be dangerous Provide adequate clearances around air openings and adequate accessibility clearance for service and proper opera...

Страница 8: ...ctronic intermittent pilot ignition system External electrical power is required to operate these units In the event of a power outage four 4 AA batteries in battery holder provide backup power for fi...

Страница 9: ...ds These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation Report No F13 094 to ANSI Z21 88 in Canada CSA 2 33 and CAN CGA 2 17 M91 in both USA and Canada a...

Страница 10: ...be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa The appliance must be isolated from the gas supply piping sy...

Страница 11: ...ons 248 C M R Sections 4 00 through 8 00 Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not ex...

Страница 12: ...itioning ducting These direct vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for l...

Страница 13: ...inimum 2 ft minimum Lowest discharge opening H H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flash...

Страница 14: ...de corner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 9...

Страница 15: ...material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Hearth Extension A hearth extension is not required wit...

Страница 16: ...encroach the area defined by the fireplace front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the fireplace face Figure 40 Non combustible mater...

Страница 17: ...Page 40 Gas Connection 14 Connect the Gas Line Page 41 15 Verify Proper Fireplace Operation Page 42 Finishing 16 Optional Install the Firebox Liners Page 43 17 Install the Logs Volcanic Stone and Glow...

Страница 18: ...1 25 5 8 651 12 1 8 308 5 1 2 140 35 35 3 8 899 59 1 2 1511 42 1 8 1070 30 1 4 768 14 1 4 362 6 5 8 168 40 40 3 8 1025 63 7 8 1622 45 3 8 1153 33 1 4 845 15 7 8 403 8 1 2 216 45 45 3 8 1153 70 3 8 178...

Страница 19: ...framing Pipe coupling recommended 5 1 4 140 mm 3 77 mm Proper Sizing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installe...

Страница 20: ...from rear venting and proceed with fireplace installation If you require a top vented unit use the following steps to convert the fireplace before use Outside preparation of the fireplace for top vent...

Страница 21: ...tep 3 Top of front fireboard standoff should be flush with top standoffs not shown Step 4 Fireboard standoff can be secured to the capture screw holes 6 Rough in the Electrical Supply if Needed As nec...

Страница 22: ...he fireplace to the side framing members using the unit s nailing flanges one top and bottom on each side of the fireplace front Figure 11 Use 8d nails or the equivalent Figure 11 Nailing Flanges Side...

Страница 23: ...25 ft Maximum horizontal run flat to near level 60 ft Maximum vertical run 60 1 9 25 Horizontal Distance ft Vertical Height ft from top of unit Vertical Height ft 2 5 Elbow 5 10 15 3 Base wing 3 Base...

Страница 24: ...telescopic vent section SV4 5LA may be used to provide the installer with an option to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a u...

Страница 25: ...465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1...

Страница 26: ...is specified in ANSI Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the g...

Страница 27: ...c space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer with 8d nails or other...

Страница 28: ...proof caulking 11 Install the storm collar Install the storm collar supplied with the flashing over the vent flashing joint Figure 22 Loosen the storm collar screw Slide collar down until it meets the...

Страница 29: ...RNING Do NOT join separate sections of concentric flexible vent pipe Figure 24 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling fire...

Страница 30: ...f vertical rise See Page 23 for more information If 20 ft of H horizontal vent run is needed then 4 ft straight section minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio...

Страница 31: ...of applications For more information on connecting the vent pipe see Page 24 Figure 25 Typical Horizontal Vent Installation Support bracket spacing every 5 ft 1 52 m Firestop Spacer Vertical Vent Fire...

Страница 32: ...s of the last section is within 7 178 mm to 11 1 4 286 mm inboard of the exterior surface to which the SV4 5HT termination is to be attached Figure 27 If the terminus of the last section is not within...

Страница 33: ...aulk Stucco Siding Interior Surface of Finished Wall Last Vent Section Use Telescopic Vent Section SV4 5LA If Necessary Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing Figu...

Страница 34: ...ate sections of concentric flexible vent together Table 21 Rear Vent No Elbows See Table 20 as an aid in venting component selection for a particular range of exterior wall thicknesses Note H is horiz...

Страница 35: ...H horizontal vent run is needed then 5 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a...

Страница 36: ...ticular range of exterior wall thicknesses If 20 ft of H horizontal vent run is needed then 4 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V ver...

Страница 37: ...N 10K81 to the inner adaptor collar approximately 1 2 from the end c Pull and extend the inner flexible vent d Slide the inner flex vent over the adaptor collar at least 1 3 4 NOTE Ensure the flex ven...

Страница 38: ...adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube to improve ease of installation 12 Complete the Field Wiring CAUTION The ground supply...

Страница 39: ...utlet s red pigtail lead Figures 32 33 Connect the white power supply wire to the outlet s common terminal 5 Connect the ground supply wire to the pigtail lead attached to the outlet s green ground sc...

Страница 40: ...ed in connecting the electronic components to the junction box in the lower compartment This grounding plug provides protection against shock hazard and should be plugged directly into a properly grou...

Страница 41: ...ed in the gas piping within the home to prevent moisture and debris in the line from damaging the valve NOTE Secure all joints tightly using appropriate tools and sealing compounds ensure propane resi...

Страница 42: ...ic units Either tighten or refasten the leaking connection and then retest as described above 3 When the gas lines are tested and leak free rinse off the leak testing solution 15 Verify Proper Firepla...

Страница 43: ...g black tip the air shutter opening may need to be adjusted If the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long ora...

Страница 44: ...ly to ensure that the proper flame appearance is achieved Figure 39 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the air shutter incrementally to a...

Страница 45: ...ed wall position framework to accommodate the thickness of the finished wall Figure 39 Combustible Wall Framing Figure 40 Face Mounting Elements Top Face Brackets Fireplace face foot slots NOTE See Co...

Страница 46: ...tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r sidence du pro...

Страница 47: ...el Description H1968 SV4 5HT 2 Horizontal Square Termination with Firestop Spacer H2246 and Adaptor 74L61 94L10 SV4 5HTSS Rigid Horizontal Small Square Termination with Firestop Spacer H2246 and Adapt...

Страница 48: ...mpressed flex 77L91 SFKIT48S Square Term for flex with 48 1219 mm compressed flex 91L66 SFGC4 6 Gear Clamp 4 5 114 mm for flex 6 pack 91L67 SFGC7 6 Gear Clamp 7 5 190 5 mm for flex 6 pack Cat No Model...

Страница 49: ...lis l installation assume les responsabilit s li es la conversion In Canada The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction an...

Страница 50: ...e affected by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furnit...

Страница 51: ...chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A...

Страница 52: ...release the access panel and lift it up and away from the fireplace Figure 41 3 Store the panel in a secure location until reinstallation Figure 41 Control compartment Figure 42 Magnetic latch barrie...

Страница 53: ...the installer for more information Check the batteries if installed at least every three 3 months to ensure they are properly charged To light the fireplace in a power outage 1 Confirm that batteries...

Страница 54: ...pilot and burner ignite but the burner extinguishes and reignites several times until the flue reaches the temperature for proper drafting To save energy switch to intermittent mode For a standing pi...

Страница 55: ...dous If the logs are not installed according to these instructions improper combustion could occur This could result in the excessive production of soot and or the colorless odorless toxic gas carbon...

Страница 56: ...nd other media see Page 55 Figure 46 Locating the log placement brackets Figure 47 Placing logs 1 and 2 3 Align the notches in the bottom of the rear log 1 with the left rear brackets Figures 51 4 Pos...

Страница 57: ...lacement brackets Figure 54 Figure 50 Locating the log placement brackets Figure 51 Placing logs 1 and 2a 2 Position rear left log 1 on the left rear log bracket Figure 55 3 Position the left front lo...

Страница 58: ...talled AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass front re...

Страница 59: ...eats evenly as the door draws shut Securely fasten the two 2 latches beneath the firebox floor to the door V flange 4 Install the barrier 5 Close the control compartment door Removing the glass door 1...

Страница 60: ...venting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodica...

Страница 61: ...e g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Page 55 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame a...

Страница 62: ...ction Look for any signs of dislocation of the vent components Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection procedure detailed in this manual Replacin...

Страница 63: ...53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone Firebox Liner Kits Traditional Models Catalog Model Description Used on F1887 MBLK33B Buff 33 Models F1886 ABLK33V Vintage Red F2187 BLK33...

Страница 64: ...ch State of the art control with touch screen operation Catalog Number Backlit LCD display Transmitter wall mounted docking station Receiver wall mounted or placed in the control compartment Thermosta...

Страница 65: ...on of the fireplace burner or blower Install the OFF ON wall switch in a convenient location near the fireplace Catalog Model 85L87 FWSK Ecoflow Control Kits Electronic Models Ecoflow Basic Remote Con...

Страница 66: ...es Direct Vent Gas Fireplaces 66 ACCESSORY COMPONENTS continued Variable Speed Wall Switch Kit The variable speed wall switch kit provides variable speed control if the optional FBK 100 blower kit is...

Страница 67: ...gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas supplier 10...

Страница 68: ...diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien q...

Страница 69: ...h has been under water Copreci Gas Valve Switches Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remo...

Страница 70: ...REFROIDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install p...

Страница 71: ...instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the connecti...

Страница 72: ...the gas supply and gas shutoff valves b Loose wires to the valve or ignition module Check control compartment for any obviously loose wiring call a service technician if necessary c Pilot flame is no...

Страница 73: ...8J53 1 1 Log Set F1883 1 F1829 1 F1830 1 F1884 1 Vent Restrictor Base H8987 1 H8987 1 H8987 1 H8987 1 Vent Restrictor Wing H8988 1 H8988 1 H8988 1 H8988 1 Door Latch Assembly H1264 1 H1264 2 H1264 2 H...

Страница 74: ...690 1 F2690 1 F2690 1 Ecoflow RF Control Module F2694 1 F2694 1 F2694 1 F2694 1 Ecoflow Power Adaptor J7930 1 J7930 1 J7930 1 J7930 1 Ecoflow Battery Holder J7931 1 J7931 1 J7931 1 J7931 1 Switch Rock...

Страница 75: ...NT PARTS continued WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or perso...

Страница 76: ...____________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________...

Страница 77: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 78: ...place serial number Date fireplace was Installed Type of gas fireplace uses Dealer name IHP reserves the right to make changes at any time without notice in design materials specifications prices and...

Отзывы: