 “F” is the single digit 5 or 6 representing powerline frequency of 50Hz or 60Hz. 

 

5

 “Ø” is either the letter I, S or B causing the phases to be individually controlled (I), controlled from “A” phase (S) or 

controlled from “D” phase (B) respectively. 
  

6

 ”S” is either the letter H or L representing high speed (H) or low speed (L) motors. 

 

7

 XX is a 2 digit number representing the voltage point above or below the set point at which slow speed pulsing 

begins. 
 

RD (read dead bands)  

Cmd:  STX ADDR RD ETX 
Rsp: 

STX ADDR AA.A

8

 BB.B

8

 CC.C

8

 ETX 

 

WD (write dead bands) 
 

Cmd:  STX ADDR WD AA.A

8

 BB.B

8

 CC.C

8

 ETX 

 

Rsp: 

STX WD ETX 

8

 AA.A BB.B CC.C are the channel A, B & C dead band setting; i.e. 00.5, 02.0,10.6  

 
NOTE:  When a dead band value is entered, the value represents the entire voltage width of the dead band. 

Example: A value of 5.0 is entered - this means ± 2.5V. The dead band minimum is .5V. 

 

RS (read set points) 

Cmd:  STX ADDR RS ETX 
Rsp: 

STX ADDR AAA.A

9

 BBB.B

9

 CCC.C

9

 ETX 

 

WS (write set points) 
 

Cmd:  STX ADDR WS AAA.A

9

 BBB.B

9

 CCC.C

9

 ETX 

 

Rsp: 

STX WS ETX 

9

 AAA.A, BBB.B, CCC.C are the channel A, B & C voltage set point values. i.e. 002.0, 048.6, 322.9. 

 
 

RV (read voltages) 

 

 

Cmd:  STX ADDR RV ETX 

 

 

Rsp: 

STX ADDR AAA.A

10

 BBB.B

10

 CCC.C

10

 DDD.D

10

 ETX 

10

 AAA.A, BBB.B, CCC.C, DDD.D are the channel A, B, C & D voltage values. i.e. 002.0, 048.6, 322.9 

 
 

KL (keypad lock toggle) 

 

 

Cmd:  STX ADDR KL ETX 

 

 

Rsp: 

STX KL ETX 

 
NOTE:  This lock method only prevents parameters from being changed. You can still view parameters with the 

phase and function select keys. The “E” key lock method prevents the entire keypad from being used except 
for the  “E” key. In the event that serial communications are lost after the keypad has been locked via the 
serial port, a hardware lockout release is provided. Open the front cover and place the calibration jumper in 
the calibration position. Press the “E” key three times in succession within a span of 2 seconds to lock the 
keypad and perform this proceedure again to unlock both types of keypad locks. If the keypad was originally 
locked with the “E” key, the lockout release needs only to be performed once. Be sure to return the 
calibration jumper to the “park” position. 

 
 
 
 

LINE-LINE TO LINE-NEUTRAL VOLTAGE TABLE 

 

If you are sensing L-N and require a L-L voltage the table on the following two 
pages will ad in determining what the FRM2000 L-N setting should be. 
 

Содержание FRM2000-1

Страница 1: ...wing models are covered in this manual FRM2000 1 FRM2000 2 FRM2000 3 Revision D Superior Electric reserves the right to make engineering changes on all its products Such refinements may affect informa...

Страница 2: ...drive on the variable transformer to control the output voltage to a desired set point within a specified dead band The unit can be programmed from an integral keypad or read and programmed remotely v...

Страница 3: ...ge OUTPUT CONTROL Contact Closure 2 per motor drive Type Solid State Relay Contact Ratings 3 0A 240VAC DISPLAY LED 5 Digits 0 5 H XXX X VAC KEYPAD ENTRY Increase Manual A Decrease Manual B Phase Selec...

Страница 4: ...4 OUTLINE...

Страница 5: ...5 CONNECTIONS A B C D...

Страница 6: ...phase and the set point for the phase that the display is currently showing To enter this mode press the D key repeatedly until bPASS appears on the display and then press the E key F 50 Used for ope...

Страница 7: ...in manual control mode If the A phase parameters are used to control B C phases A mode all three motors will operate simultaneously B Decrease Manual With the B key depressed the motor for the selecte...

Страница 8: ...ngle hexadecimal character 0 9 A F CMD A two character command for which there is a defined response DATA Information associated with the command or response data as needed some commands require no DA...

Страница 9: ...oltage set point values i e 002 0 048 6 322 9 RV read voltages Cmd STX ADDR RV ETX Rsp STX ADDR AAA A 10 BBB B 10 CCC C 10 DDD D 10 ETX 10 AAA A BBB B CCC C DDD D are the channel A B C D voltage value...

Страница 10: ...5 334 192 8 573 330 8 513 296 2 453 261 5 393 226 9 333 192 3 572 330 2 512 295 6 452 261 0 392 226 3 332 191 7 571 329 7 511 295 0 451 260 4 391 225 7 331 191 1 570 329 1 510 294 4 450 259 8 390 225...

Страница 11: ...35 20 2 274 158 2 214 123 6 154 88 9 94 54 3 34 19 6 273 157 6 213 123 0 153 88 3 93 53 7 33 19 1 272 157 0 212 122 4 152 87 8 92 53 1 32 18 5 271 156 5 211 121 8 151 87 2 91 52 5 31 17 9 270 155 9 2...

Страница 12: ...h offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available...

Отзывы: