CONTROL MODES AND FEATURES

 

 

Set Point 

This is the value to which the unit controls the output of a variable transformer. To enter a 
set point, press the “D” key until the display says “A.”, on the left side, Enter a set point and 
then press “E”.  

 
 

Dead Band 

This  is  the  tolerance  around  the  set  point  to  which  the  unit  will  keep  the  variable 
transformer. A dead band of 10 volts means ±5 volts around the set point. To enter a dead 
band, press the “D” key until the display says “Ad” on the left side. Enter a dead band in the 
form XX.X volts and then press “E”. 

 
 

“A” 

Phases  A,  B  &  C  will  all  be  controlled  by  the  A  phase  control  parameters  (set  point  and 
dead  band).  To  enter  this  mode,  press  the  “D”  key  repeatedly  until  “A”  appears  on  the 
display and then press the “E” key. 

 
 

“AbC” 

Phases  A,  B & C will be individually controlled by their respective control parameters (set 
point and dead band). To enter this mode, press the “D” key repeatedly until “AbC” appears 
on the display and then press the “E” key.  

 
 

“bPASS” 

Phases A, B, & C will be controlled to a set point equal to the voltage measured on channel 
D.  The  dead  band  will  be  set  at  1.0V.  While  in  this  mode,  the  display  will  slowly  step 
through the instantaneous voltage readings of each phase (A, B, C & D). What is displayed 
is not the instantaneous voltage; but instead the difference between the measured voltage 
on “D” phase and the set point for the phase that the display is currently showing. To enter 
this  mode,  press  the  “D”  key  repeatedly  until  “bPASS”  appears  on  the  display  and  then 
press the “E” key. 

 
 

“F 50” 

Used  for  operation  on  50Hz  power.  To  set  the  unit  for  50Hz  operation,  press  the  “D”  key 
repeatedly until “F 50” appears on the display and then press the “E” key. 

 
 

“F 60” 

Used  for  operation  on  60Hz  power.  To  set  the  unit  for  60Hz  operation,  press  the  “D”  key 
repeatedly until “F 60” appears on the display and then press the “E” key. 

 
 

“HI XX” 

Used for operation with high speed motors (motor speeds less than 10 seconds). XX is a 2 
digit  number  entered  from  the  keypad  representing  the  voltage  point  above  or  below  the 
set  point  at  which  slow  speed  pulsing  begins.  When  the  instantaneous  voltage  is 
approaching  the  set  point  and  reaches  this  value,  the  motor  transitions  from  moving 
continuously  to  moving  in  pulses  in  an  effort  to  prevent  an  overshoot  of  the  set point. To 
set the unit for a high speed motor, press the “D” key repeatedly until “HI” appears on the 
left side of the display; and then enter a 1 or 2 digit numerical value up to 25 representing 
volts. Press the ”E” key. 

 
 

“LO XX” 

Used  for  operation  with  low  speed  motors  (motor  speeds  greater  than  10  seconds).  The 
explanation  on  why  this  is  needed  can  be  read  in  the  explanation  for  “HI  XX”.  To  set  the 
unit for a low speed motor, press the “D” key repeatedly until ‘LO” appears on the left side 
of  the  display;  and  then  enter  up  to  a  1  or  2  digit  numerical  value  up  to  25  representing 
volts. Press the “E” key. 

 

Содержание FRM2000-1

Страница 1: ...wing models are covered in this manual FRM2000 1 FRM2000 2 FRM2000 3 Revision D Superior Electric reserves the right to make engineering changes on all its products Such refinements may affect informa...

Страница 2: ...drive on the variable transformer to control the output voltage to a desired set point within a specified dead band The unit can be programmed from an integral keypad or read and programmed remotely v...

Страница 3: ...ge OUTPUT CONTROL Contact Closure 2 per motor drive Type Solid State Relay Contact Ratings 3 0A 240VAC DISPLAY LED 5 Digits 0 5 H XXX X VAC KEYPAD ENTRY Increase Manual A Decrease Manual B Phase Selec...

Страница 4: ...4 OUTLINE...

Страница 5: ...5 CONNECTIONS A B C D...

Страница 6: ...phase and the set point for the phase that the display is currently showing To enter this mode press the D key repeatedly until bPASS appears on the display and then press the E key F 50 Used for ope...

Страница 7: ...in manual control mode If the A phase parameters are used to control B C phases A mode all three motors will operate simultaneously B Decrease Manual With the B key depressed the motor for the selecte...

Страница 8: ...ngle hexadecimal character 0 9 A F CMD A two character command for which there is a defined response DATA Information associated with the command or response data as needed some commands require no DA...

Страница 9: ...oltage set point values i e 002 0 048 6 322 9 RV read voltages Cmd STX ADDR RV ETX Rsp STX ADDR AAA A 10 BBB B 10 CCC C 10 DDD D 10 ETX 10 AAA A BBB B CCC C DDD D are the channel A B C D voltage value...

Страница 10: ...5 334 192 8 573 330 8 513 296 2 453 261 5 393 226 9 333 192 3 572 330 2 512 295 6 452 261 0 392 226 3 332 191 7 571 329 7 511 295 0 451 260 4 391 225 7 331 191 1 570 329 1 510 294 4 450 259 8 390 225...

Страница 11: ...35 20 2 274 158 2 214 123 6 154 88 9 94 54 3 34 19 6 273 157 6 213 123 0 153 88 3 93 53 7 33 19 1 272 157 0 212 122 4 152 87 8 92 53 1 32 18 5 271 156 5 211 121 8 151 87 2 91 52 5 31 17 9 270 155 9 2...

Страница 12: ...h offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available...

Отзывы: