Suparule Systems Ltd
Page 15 of 24
CFZ DCF2038 v1.09
Sensorform EFI
Automatic Reset
On return of network power (minimum 10A flowing in the phase conductor to
which the Power CT is attached) the unit will validate the presence of power for
a continuous period of 10 seconds, following which the device will
automatically clear the tripped state. This will latch the Aux. Relay to a reset
position (open) and reset the Mechanical Flag indicator to the OFF (Black)
state.
NOTE: In the event of the internal backup power supply being fully discharged,
the minimum charge-up time is needed, before the tripped state can be reset.
Manual Reset
The Test/Reset button can be used to manually reset the unit from a tripped
state. To do this the Test/Reset button must be pressed for a minimum period
of 3 seconds.
The Remote Reset input can also be used to manually reset the unit from a
tripped state. To do this, the input to the Remote Reset should be shorted
(closed) for a minimum of 3 seconds.