3-level Teaching
This is a method of setting the ON and OFF range by
three levels (P-1, P-2, P-3) teaching and set the OFF
level or ON level at the middle of ‘A’ and ‘B’ (1_SL) and
set the ON level or OFF level at the middle of ‘B’ and
‘C’ (2_SL).
After teaching, P-1, P-2 and P-3 are automatically
assigned in ascending order to ‘A’, ‘B’, and ‘C’.
Time
A
1_SL
2_SL
B
C
0
ON
OFF
Incident light intensity
9,999
Output
(L-ON)
Press the
MODE key once.
Blinking by turns.
Press the
Jog switch.
Incident light
intensity for P-1.
Press the
Jog switch.
Incident light
intensity for P-2.
The status condition (A) when incident light
is the lowest intensity.
The status condition (B) when the incident light
intensity is between lowest and greatest.
1
Select ‘TEACH mode’ by pressing the [MODE key] once.
2
The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’ setting state.
3
If the [Jog switch] is pressed while in the status condition (A)
when the incident light is the lowest intensity, then the
display will blink the incident light intensity reading (red).
4
The amplifier has entered the ‘P-2’ setting state and ‘ ’
(green) will blink.
5
If the [Jog switch] is pressed while in the status condition (B)
when the incident light intensity is between lowest and
greatest, the display will blink the incident light intensity
reading (red).
20