4 Product Installation
Figure 4-47 Monitoring device installation
Terminal definition:
No.
1
2
3
4
5
6
Definition
COM/DRMO
REFGEN
/
/
/
/
※ 4.6 Monitoring Device Installation
Sunways STH 3~8kW series hybrid inverter can be monitored through either WiFi or LAN, and
you can alternatively select according to your preference.
Plug the WiFi or LAN module into the Com1 port in the bottom of inverter by following the
direction the side with indicator is up (as shown in Figure 4-47). A slight “click” sound
during the installation represents that the assembly is in place.
Note
①
The WiFi version module needs to be configured to the router for the first installation. If the router name or
password are changed, the WiFi dongle will need to be reconfigured. For details, please refer to the [QUICK IN-
STALLATION GUIDE] which is attached to the accessory bag.
②
If DHCP is enabled on the router, the LAN version module does not need to be configured. Otherwise, please
refer to the [QUICK INSTALLATION GUIDE] which is attached to the accessory bag.
5 Start and Stop
※ 5.1 Start Inverter
When starting the inverter, follow these steps:
① Turn the DC switch in the inverter bottom to the “ON” position.
② Turn on the lithium battery switch.
③ Switch on the AC breaker first.
④ The inverter will start to check the DC and AC input parameters and self-check, and if ev-
erything is normal, the inverter will start to work according to the work mode which you set
on the App. The inverter display and indicators will show relative parameters and status.
※ 5.2 Stop Inverter
When turning off the inverter, please follow the steps below:
① Shut off the inverter through the APP or the button on the display first.
② Disconnect the breakers on the grid and load side.
③ Turn off the battery switch, and disconnect the DC breaker on the battery side (if any).
④ Wait 30 seconds and then turn the inverter DC switch to the “OFF” position. At this time,
there is remaining power in the inverter capacitor. Wait for 5 minutes until the inverter is
completely de-energized before operating.
⑤ Disconnect the AC and DC cables.
5 Start and Stop
Содержание STH 3-8kW Series
Страница 36: ......