and go to the front screen.
10.3.2. Fuel-dependent service settings.
To enter these settings, you need to en
-
ter the main screen for service settings
on the line
"Settings. Combustion ”
,
press button, then select fuel and press
button again
.
Cleaning -
From this menu the duration
of the cleaning cycles is set, with the op
-
erating time of the main and additional
cleaning fan. Here it is set whether to
have cycles for automatic cleaning and
during what period to be. The automatic
cleaning cycles are in the following se
-
quence: extinguishing, cleaning after
extinguishing and re-ignition. The clean
-
ing procedures are performed before
ignition (Start row), after extinguishing
or during automatic cleaning (Stop row)
and with a registered
"Reverse combus-
tion"
alarm (Alarm row).
Ignition -
this menu sets the number of
ignition attempts (ignition tests), fuel
auger operation time for refueling the
first pellet dose (Refueling), chimney fan
speed during the entire ignition period
(chimney vent) and maximum duration
at each of the three stages of ignition, as
well as the speed of the main fan during
each stage.
If the photosensor detects
an ignited fire, the ignition
procedure
is
stopped
immediately and switched to
ignition!
Ignition -
adjusts the process of smooth
ignition to stabilize the fire after ignition.
The upper field adjusts the fan speed,
main and chimney, as well as the dura
-
tion (Duration [sec]) of the burning pe
-
riod of the first dose. No new pellets are
fed during the first dose incineration.
In the lower field, the retention time
of each power is set in the process of
gradual increase of the power from the
smallest P1 to reaching the nominal one,
according to the temperature of the wa
-
ter in the boiler.
D1>Kinding
Burning first dose
Duration (sec)
Fan
Chimney fan
Smoothly kinding
(sec)
(sec)
Field
Continued. (sec)
-waiting time to
burn the first dose and fan speed
Field
Smooth-burning
- After burning
the first dose, 60 seconds will work with
power P1 and another 60 with power P2.
Power P1, Power P2, Power P3, Main-
tenance -
the same type of menus for
setting the operating parameters for
each power from the smallest P1 to that
for maintaining the fire. In order to ac
-
curately dispense the amount of pellets,
the Portion line, which is the operating
time of the fuel auger, and the Cycle line,