4.1.3. Electrical Installation
Mains low-voltage power distribution room Charging pile pre-stage distribution box AC charging pile
Electric vehicle.
Charging pile input incoming line connection:
The device must be grounded. The firewire (L) neutral wire (N) must be tested with the test pencil. The
electric pen test is lit by the firewire (L), and then the L wire and the N wire are respectively connected to
the corresponding terminals!
Safety Warning: In order to ensure safe charging, the user must strictly follow the phase sequence of the
incoming terminal when wiring the input. At the same time, the charging pile with a rated current of 32A,
the incoming input line is not less than 6 square copper core wire; the charging pile with the rated current
is 16A, the incoming input line is not less than 4 square copper core wire. (After wiring is completed, put
it back into the lead wire of the column or protect it with a protective cover to prevent accidental exposure.)
The following safety regulations are observed when charging and wiring the charging pile:
No.
Item
Safety rules
Instruction
1
Charging pile preamplifier
The circuit breaker must be installed in the
front stage of the charging pile input power
supply: Rated current 32A, circuit breaker
selection 40A.
The
charging
pile
is
effectively isolated from the
power grid when there is a
safety problem during use.
2
Charging pile
incoming line
phase sequence
Wire in strict accordance with the phase
sequence of Figure A
Ensure charging safety.
3
Charging pile
entry line
diameter
Rated current 32A, wire diameter not less
than 6mm
2
.
When charging normally,
the cable does not generate
heat due to large current.
4
Input power
parameter
Make sure the input power parameters
match the charging stub.
Ensure charging safety.
5
Charging pile
line process
Exposed wiring must be protected by
effective measures such as conduits to
avoid crushing or scratching the wires.
Protect
the
line
from
damage.