background image

 

Hybrid Parity (Super) Inverter 

 

INSTALLER MANUAL 

3.6kW/5.5kW/8.8kW PLUS PARALLEL VERSION 

 

 
 

 

Global Tech China Ltd, 3 Floor, Wai Yip Industrial Building.171 Wai Yip Street, 

Kwun Tong, Kowloon, Hong Kong. 

Tel: +852 2884 4318 Fax: +8522884 4816 

www.sunsynk.com / [email protected] / www.globaltechhk.com

 

 

 

Содержание G01LP1-US/EU

Страница 1: ...3 6kW 5 5kW 8 8kW PLUS PARALLEL VERSION Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 4816 www sunsynk com sal...

Страница 2: ...21 4 5 SYSTEM FLOW PAGE 22 4 6 SETUP PAGE 23 4 7 SET TIME CLOCK 23 4 8 SET COMPANY NAME BEEPER AUTO DIM 24 4 9 FACTORY RESET AND LOCK CODE 25 4 10 BATTERY SETUP HOME PAGE 25 4 11 GENERATOR AND BATTERY...

Страница 3: ......

Страница 4: ...must be correctly grounded and the supply line must be equipped with a suitable breaker and RCD to protect people The unit is not explosion proof so it should not be installed in an explosive atmosph...

Страница 5: ...nd off grid COMPATIBLE Compatible with main electrical grid voltages or power generators Compatible with wind turbines 220V single phase pure sinewave inverter Self consumption and feed in to the grid...

Страница 6: ...ction Smart battery charger design for optimized battery protection Limiting function installed to prevent excess power overflow to grid APPLICATIONS Marine vessel power management Power shedding home...

Страница 7: ...x AC Output Current A 18A 25A Max Continuous AC Passthrough A 35A Power Factor 0 8 leading to 0 8 lagging Output Frequency and Voltage 50 60Hz 220 230 240Vac single phase Grid Type Single Phase Curren...

Страница 8: ...rated power 10 S AC Output Rated Current A 20 8A 25A 31 7A 33A 33 4A 35A Max AC Output Current A 24A 28 8A 36 4A 38A 38 3A 40A Max Continuous AC Passthrough A 48A 80A 90A 90A Output Frequency and Volt...

Страница 9: ...er Inverter 3 6kW 5 5kW 8 8kW Plus Parallel Version www sunsynk com Weight kg 32 Size Length x Width x Height 670 x 420 x 233 mm Protection Degree IP65 Installation Style Wall mounted Warranty 5 years...

Страница 10: ...chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Areas that can cause combustible gas to leak which contains suspended carbon...

Страница 11: ...e wall where the height from the floors is higher than 1600mm 3 2 Mounting the inverter Select installation locations that adequate to support the weight of the converter Install this inverter at eye...

Страница 12: ...nd the inverter It is recommended to utilize a suitable fuse and DC isolator see next page In some applications switching devices may not be required but overcurrent protectors are still required A mi...

Страница 13: ...Battery for setting it up in the inverter 1 Connect a properly power cable following the battery manufacturer specification and recommend safety devices 2 Connect communication cable properly followin...

Страница 14: ...apable of controlling the batteries BMS Therefore you need to set the protocol of the BMS on both the battery and the inverter WHEN USING MORE THAN ONE BATTERY THE FIRST BATTERY WILL BE THE MASTER AND...

Страница 15: ...tied inverter It is both an in and out connection for non essential load and supply LOAD Connection of essential loads such as lighting security systems and internet Recommended AC Surge Protector Ple...

Страница 16: ...ignal Island Mode on the battery charge menu click on the gear icon battery icon as shown in the figure below You can test that there is a voltage when the inverter is disconnected from the grid by us...

Страница 17: ...T See below for information to determine if the CT coil is connected the correct way around 1 First of all ensure that the CT is measuring some power flowing into the house inverter by switching off t...

Страница 18: ...Amp as shown below Before connecting to PV modules install a separate DC circuit breaker between the inverter and PV modules To avoid any malfunction do not connect any PV modules with possible curren...

Страница 19: ...nection normal AC Green LED solid light Grid connection normal Normal Green LED solid light Inverter functioning normally Alarm Red LED solid light Fault Function Key Description Esc To exit the previ...

Страница 20: ...utton any page to access the home page Daily readings Real time readings What this page displays Total daily power into the battery kWh Total daily power out of the battery kWh SOC State of charge of...

Страница 21: ...tive When receiving from the grid the power is positive If the sign of the grid and HM powers are not the same when the PV is disconnected and the inverter is only taking energy from the grid and usin...

Страница 22: ...m take a look at the figure bellow 1 The PV modules charge the batteries 2 When the batteries reach a specific level programmable the battery power is fed into the inverter 3 The inverter can then sup...

Страница 23: ...codes Set up Li BMS press Li BMS 4 7 Set Time Clock To set time click on the Basic icon and then on Time How to set up step by step 1 Touch the screen on the variable that you want to change 2 Change...

Страница 24: ...rows up and down and then select ok This will change the name on the home screen How set the auto dim Set a number in the auto dim box to dim the LEO after a number of seconds How to activate deactiva...

Страница 25: ...gure battery settings click on the Battery icon and then on Batt type What you can do from this page Use battery voltage for all settings V What this page displays Reset status Whether lock code is us...

Страница 26: ...auto switch a relay box Tick Grid Charge signal to auto switch a relay box IMPORTANT TO PROTECT YOUR BATTERY AND INVERTER 200Ah AGM battery max charge discharge current 40Amps 400Ah AGM battery max ch...

Страница 27: ...oth the discharge and recharge efficiency NOTE Shutdown causes the inverter to enter standby mode It will not completely shut down the inverter The total shutdown is below 19V What this page displays...

Страница 28: ...end of the BULK mode absorption voltage an equalisation voltage but technically it s not Higher capacity wet flooded batteries sometimes benefit from this procedure particularly the physically tall b...

Страница 29: ...examined tested and approved by Sunsynk Brand Model RS485 or CAN Inverter Setup Notes Pylon or Equivalent US2000 CAN 0 RS485 5 US20000 PLUS CAN 0 RS485 5 DYNESS B4850 CAN 0 Short Lione 6 7 at inverter...

Страница 30: ...e when it needs to occur Define the time to discharge to the load or export to the grid by unticking Grid and Gen IMPORTANT When not using communications between battery and inverter never overcharge...

Страница 31: ...trols the maximum overall power both to the load and grid ports combined It is set to low if an over current fault occurs 6 Tick this box if you wish that the solar panels prioritize power to the load...

Страница 32: ...et as 100W in this case to prevent any backflow In this example the PV generator prioritizes to supply the load first and then to charge the battery secondarily 4 15 Grid Supply Voltage and Frequency...

Страница 33: ...cessary to set three inverters as master and three as slaves Phase A Master A and Slave A Phase B Master B and Slave B Phase C Master C and Slave C For stability all the batteries need to be connected...

Страница 34: ...set to slave Each inverter must have a unique Modbus number Each set of inverters must be set to the same phase For example when paralleling three inverters in a three phase utility grid all must be...

Страница 35: ...t F46 on the display What are the consequences of not setting one inverter in a parallel mode It can damage the inverter What are the consequences of having more than one master or none set to master...

Страница 36: ...This page shows the daily monthly yearly and total solar power produced Access this page by clicking on the Solar Turbine icon on the home page 4 18 Grid Power This page shows the daily monthly yearl...

Страница 37: ...00 3500 300 11 67 3500 400 8 75 3500 What this page displays If one or both of the MPPTs are connected to a wind turbine What you can do from this page Select the MPPT to be used as a turbine input I...

Страница 38: ...h to flow This can be done using a switch on by the smart load option or utilizing a wind turbine controller with a built in dump load Also the hot water tank controlled via smart load can act as a go...

Страница 39: ...el when the Aux load switches off Aux Load on Battery or Voltage Battery level when the Aux load switches on Solar Power Power limiter to the maximum power allowed to the Aux load Gen Input Tick this...

Страница 40: ...x Load icon Peak Shaving It is a technique used to reduce electrical power consumption during periods of maximum demand on the utility grid Thus one can save substantial amounts of money due to peakin...

Страница 41: ...ation date 4 The problem description including the fault code and indicator status displayed on the LCD is as detailed as possible 5 Your contact information Error Code Description Solutions F13 Worki...

Страница 42: ...w voltage Grid voltage fault 1 Check if the voltage is in the range of standard voltage in specification this can be adjusted via the grid set up page 2 Check if grid cables are correctly connected F4...

Страница 43: ...Failure F43 AC_VW_OverVolt_Fault F12 AC_SlaveContactor_Failure F44 AC_VW_UnderVolt_Fault F13 Working_Mode_change F45 AC_UV_OverVolt_Fault F14 DC_OverCurr_Failure F46 AC_UV_UnderVolt_Fault F15 AC_OverC...

Страница 44: ...uestions www sunsynk com NOTE The energy storage inverter is designed according to the grid connected operation The inverters meets the safety and electromagnetic compatibility requirements as establi...

Страница 45: ...8kW Plus Parallel Version www sunsynk com Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 4816 www sunsynk com sa...