MILLIVOLT SYSTEM
The millivolt system and 

individual components may 

be checked with a millivolt 

meter having a 0-1000 MV 

range (900-040). Before 

checking system, be certain 

wall thermostat lead wire 

does not exceed length (as 

recommended in the WIRING 

section table), and all con-

nections are clean and tight. 
Conduct each check, shown 

in the chart shown at right, 

by connecting the meter test 

leads to the terminals, as 

indicated. All the readings  

are closed circuit. 

Millivolt model heaters
Lighting the pilot and burners

Model 3020-M, 2618-M, 2016-M, 3020-M/M, 2618-M/M

Lighting and relighting procedures for all 2010 and later models
1.  Light the left hand burner first (facing the heater). Turn the knob to pilot, and push down. 

Push the piezo ignitor repeatedly till the pilot lights. Hold the control knob down till the pilot 

stays lit approximately 1 minute. If it goes out, repeat till it stays on. Note: before lighting  

the pilot, turn the wall thermostat to 80°F.

2.  The right hand burner is a secondary burner on all two control units. You must turn the knob 

to pilot, push down and hold for 30 seconds. Release and turn on high (for extra heat).

CAUTION: Keep combustible material away from gas appliance. Keep burner area clean and 

free of dust and lint.

Inlet

Outlet

Содержание 2016-M

Страница 1: ...WARNING Please read carefully before operating your SUNRISE ROOM HEATER Owner s Manual for ROOM HEATERS...

Страница 2: ...CONNECTION Install the fitting into the pilot gas tapping turning until finger tight Insert clean debarred tubing all the way through the fitting Holding the tubing securely slowly tighten the fittin...

Страница 3: ...temperature control knob to high counter clockwise Hold the red button down and push the piezo ignitor repeatedly until the pilot light stays lit approximately 30 seconds If the pilot light goes out r...

Страница 4: ...0 M 2618 M 2016 M 3020 M M 2618 M M Lighting and relighting procedures for all 2010 and later models 1 Light the left hand burner first facing the heater Turn the knob to pilot and push down Push the...

Страница 5: ...aterial to change to L P or natural gas operation as desired 6 Replace cap and tighten 7 Check outlet pressure with pressure gage at outlet pressure tap to determine if the gas valve is functioning wi...

Страница 6: ...er and air mixer Adjust air intake Call your service technician for assistance Q The thermostat doesn t light A See proper section on how to light the heater Hydraulic thermostat page 3 Millivolt page...

Страница 7: ...higher than the heater Hood should be 1 2 3 4 wider than heater on all four sides See diagram Overall Height Varies approx 60 12 3 8 19 5 21 2 x 10 Floor Joist Side View 12 x 14 Main Register Basement...

Страница 8: ...the room temperature at the selected temperature at the selected temperature until the next program period begins Then the thermostat will automatically revert to the program HOLD TEMPERATURE The ther...

Страница 9: ...t heating program period The start time is 6 00 AM and 70 is the programmed temperature this example reflects factory pre programming 3 Press or to change the displayed temperature to your selected te...

Страница 10: ...02 Hydraulic Gas Valve LP x x x 0710 501 Hydraulic Gas Valve NG x x x IMBU 6 6 Burner Import USBU 6 6 Burner US x x x x x BU Sleeve Burner Sleeves x x x PI Tube Pilot Tubing 22 Flex 3 3 8 3 Flex Conne...

Страница 11: ...11 Millivolt System Hydraulic System 32 1 30 1 31 1...

Страница 12: ..._____ ____ ____ 20___ _____________________________________________ ____ ____ 20___ _____________________________________________ ____ ____ 20___ _____________________________________________ ____ ___...