Sunpak® Infrared Heaters 

Ventilation 

1.  It is required that areas above the heater be 

properly vented to allow for necessary combustion 

air and removal of combustion gases. 

2.  Heaters shall be provided with natural or 

mechanical means to supply and exhaust at least 

4 cfm per 1,000 BTU per hour of heater input. 

Exhaust openings for removing the flue products 

shall be above the level of the heaters. 

3.  Heater ventilation must comply with state and local 

codes

. Never use heater in a fully enclosed 

area

Fire Sprinklers 

Fire Sprinklers must be located at an appropriate 

distance from each heater to avoid accidental activation of 

the sprinkler. Ethylene glycol or propylene glycol must 

never be used in fire sprinkler systems where heaters are 

present as these substances may become flammable 

when heated.  A fire sprinkler professional must be 

consulted when heaters are installed where fire sprinklers 

are present to insure that heaters and the fire sprinkler 

system are properly integrated. Specific guidelines can be 

found in NFPA 13 regarding design and specifications for 

Fire Sprinkler Systems near heaters.

 

 

Initial Start-

Up Procedure  

(Read entire Procedure First) 

1.  Before turning ON your new heater make sure: 

a.  Heater is securely mounted and clearances from 

combustible materials have been observed (see 

Clearances – page 7); 

b.  Tip angle of heater does not exceed 30 degrees 

(see Correct Mounting – page 12); 

c.  Gas line is properly connected and there are no 

leaks (see Gas Piping – page 8); 

d.  Make sure 24 VAC is properly connected to the 

heater. Applying 120 VAC to the heater will 

damage the switch and other heater controls 

2.  Start Heater; 

a.  Turn ON manual gas valve. 

b.  Set switch to the high setting for the first 5 

minutes. 

c.  If heater locks out, switch to OFF to RESET 

Heater and repeat start up sequence. 

d.  If the heater locks out several times there may still 

be air in the gas line. 

 

NOTE: Some white smoke may appear 

during or just after the initial start-up of the 

heater. White smoke will dissipate with 

proceeding use.  This is normal due to some 

residual lubrication on a new heater 

Regular Service and Maintenance 

Over time, particularly during long periods of non-

use, the heater can accumulate dirt and debris in 

and around the pilot and the burner. Routine 

maintenance should be performed at least once a 

year by a qualified service agency to insure the 

heater is operating properly. More frequent 

service may be required for heaters located near 

waterfronts. If local service is not available call 

your natural gas or propane supplier. 

 

 

Sunpak Pilot and Electrode Position 

 

____________________________________ 

 

 

Typical 24V Transformer. Transformer should 

never be mounted inside heater 

Содержание S34-TSH

Страница 1: ... and experienced in the installation and repair of this type of equipment and related system components WARNING California Proposition 65 Warning IF NOT INSTALLED OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS THIS PRODUCT CAN EXPOSE YOU TO SUBSTANCES IN THE FUEL OR FROM COMBUSTION INCLUDING CARBON MONOXIDE RESULTING IN DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO TH...

Страница 2: ...sidential indoor spaces may result in death asphyxiation serious injury or property damage Storage of gasoline and other flammable vapors and liquids in the vicinity of this or any other appliance may result in fire or explosion DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Always maintain clearance to combustibles as specified Hi...

Страница 3: ...fety sensor fails to sense flame at the pilot the heater will shut down and lockout This may happen due to low gas pressure or a gusty wind To restart the heater first set the switch to OFF before restarting the heater Although these heaters are designed for outdoor installation and use it is important that switches transformers or other operating controls be protected from the weather The TSH Swi...

Страница 4: ... down Note that the top clearances required from combustible material increases when heaters are at an angle The heater must always be horizontal to the floor Never mount the heater in the vertical position Breezy conditions must be considered when heating any patio Windbreaks can be extremely effective in increasing comfort and reducing heating costs Windbreaks must be designed in such a way as t...

Страница 5: ...Sunpak S34 TSH Infrared Heaters 5 ...

Страница 6: ...Sunpak S34 TSH Infrared Heaters 6 Warning Heater must be level in the lengthwise direction ...

Страница 7: ...rt 1 applies Gas Supply The gas inlet supply pressure and manifold pressures required for each heater are listed below For gas supply line pressures in excess of PSI consult with your gas service provider or the factory Gas Inlet Pressure Nat Gas Propane Maximum Pressure PSI PSI Minimum Pressure 6 W C 11 W C Manifold Pressure 5 W C 10 W C It is critical that the gas piping system be adequately siz...

Страница 8: ...ergency shutoff to the unit 2 Check with local and state plumbing and heating codes regarding sizing of gas lines 3 All gas pipe connections to the heater s must be sealed with a gas pipe compound resistant to liquefied petroleum gases 4 Installation of a drip leg or sediment trap in the gas supply line going to each heater is required to minimize the possibility of any loose scale or dirt within ...

Страница 9: ...ed and clearances from combustible materials have been observed see Clearances page 7 b Tip angle of heater does not exceed 30 degrees see Correct Mounting page 12 c Gas line is properly connected and there are no leaks see Gas Piping page 8 d Make sure 24 VAC is properly connected to the heater Applying 120 VAC to the heater will damage the switch and other heater controls 2 Start Heater a Turn O...

Страница 10: ... Optional Face Trim can be easily installed on all Sunpak models You must remove the Sunpak Face Trim to connect power to the heater The Sunpak Face Trim is secured with four 4 screws two 2 located along each side of the heater ...

Страница 11: ...Sunpak Infrared Heaters 11 ...

Страница 12: ...Sunpak Infrared Heaters 12 ...

Страница 13: ...Sunpak Infrared Heaters 13 ...

Страница 14: ...y Page 7 Gas Piping Page 8 Lack of Fresh Air to Heater Adjust tip angle to less than 30 degrees Add ventilation to patio above and below heater Ventilation Page 9 Dirty Orifice Clean orifice Regular Service Maintenance Page 9 Dirty Burner Use bottle brush to clear any cobwebs or debris from mixer tube of burner Use compressed air under 30 psi to blow through ceramic eye protection required Poor He...

Страница 15: ... charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor c All costs necessary or incidental for handling and administrative charges and for any materials and or permits required for installation of the replacement heater or part LIMITATION ON IMPLIED WARRANTIES Implied warranties including any wa...

Отзывы: