background image

 

 

 

Use the following settings. Temperatures are averaged over one month:  
 
For Stand-alone systems: 

Controller type 

Setting 

-20 to 0°C 

0 to 15°C 

15 to 35°C 

>35°C 

Constant  Voltage  –  one 

step 

 

Vr 

 

2,37V 

 

2,35V 

 

2,30V 

 

2,27V 

 

Constant  Voltage  –  two 
steps 

absorption 
maximum 2 h per day 

 

2,40V 

 

2,40V 

 

2,35V 

 

2,30V 

float 

2,35V 

2,30V 

2,25V 

2,25V 

 

On-off 

High voltage (Vr) 

2,40V 

2,35V 

2,30V 

2,30V 

Low voltage (Vrr) 

2,20V 

2,20V 

2,20V 

2,20V 

 

For hybrid systems: 

    

when only PV is engaged: use settings as in “Constant Voltage – one step” case above 

    

when only diesel is engaged (continuously): reduce the previous settings by 0.05V each. 

 

3.4.      Temperature limits

 

All  technical  data  apply  for  the  nominal  temperature of  20

o

C.  The  ideal  operating  temperature range  is  20

o

C  to 

25

o

C.  The  recommended operating temperature range  is  15

o

C  to  35

o

C.  Higher  temperatures reduce  the  working 

life. A maximum temperature of 45

o

C must not be exceeded. In hybrid applications the yearly average of battery 

temperature should be less than 30°C. 

Subzero temperatures may cause electrolyte freezing and irreversible damage when the battery’s state of charge 
(SoC) is low. The minimum safe temperature Vs SoC is given below: 

 

SoC (% to C10 – DIN value) 

0% – 40% 

40% – 60% 

60% – 80% 

Freezing point 

-30 

o

-20 

o

-15 

o

 

The  system  designer/installer  shall  consider  countermeasures  like  thermal  insulation,  increasing  the  battery 
capacity or increasing the minimum system voltage. In Stand-alone systems it is recommended to use controllers 
with adjustable LVD setting to the battery temperature (higher LVD for lower temperature). 

 

During operation, the temperature difference between individual battery cells should be below 3

o

K. 

 

3.5.      Current limits

 

The maximum charging current during the bulk charging is 0.2 x C10, while the battery voltage is below the 

gassing voltage of 2,40V x number of cells. 

 

3.6.      Ripple currents

 

During  recharging  up  to  2.40  V/cell,  the  effective  value  of  the  AC  ripple  current  may  reach  temporarily  at 
maximum  10  A  /100  Ah  C10  nominal  capacity.  After  recharging  and  at  float  charge  in  stand-by  or  buffer 

operation, the effective value of the AC ripple current must not exceed 5 A /100 Ah C10 nominal capacity. 

 

4.        Battery Maintenance

 

To avoid leakage currents and the associated risk of fire, keep the battery dry and clean. Clean with clear water 
and do  not  use  any  solvents and  detergents  as  they  can  cause  permanent  damage  to  container  or  lid.   Avoid 
electrostatic charges. 
 

To be checked and listed every 6 months: 

    

battery voltage 

    

voltage of some cells (pilot cells) 

    

temperature of the container in some cells (pilot cells) 

    

confirm daily DoD per cell 

    

confirm max DoD per cell does not exceed the allowed limit 

    

confirm charging factor is within acceptable limits 

    

confirm that charge settings correspond to the recommended ones 

    

finally check if corrective equalizing is applied according to 3.2.2.2 

 
Check and list every 12 months: 

    

The voltages and temperatures in all cells. 

    

Connectors, racks and ventilation. 

 
 
 

Содержание RES SOPzV Series

Страница 1: ...ply with the OPERATING INSTRUCTIONS repairs carried out with non approved spare parts or unauthorized interference with the battery will invalidate any claim for warranty SYSTEMS SUNLIGHT S A Headquarters 2 Ermou Nikis Str Syntagma Square 105 63 Athens Attica Greece T 30 210 6245400 F 30 210 6245409 Manufacturing Plant Neo Olvio 672 00 Xanthi Greece T 30 25410 48100 F 30 25410 95446 Service Depart...

Страница 2: ...tically up and equally on each of the poles Never drag or roll the battery since damage will be caused Do not apply force to the safety valve during handling The batteries are fully charged before shipment Do not short circuit Check for evidence of leakage All cells with visible defects such as cracked jars loose terminal posts or other unrecoverable problems shall be rejected 2 Installation and c...

Страница 3: ... correct torque loading of 22 Nm Electrical connections to the battery and between cells on separate levels or racks should be made to minimize mechanical strain on battery terminal posts For systems where the total battery voltage is measured at the controller use oversized cables to the battery in order to minimize the voltage drop Check the battery s total voltage It should match the number of ...

Страница 4: ...erature stays within the allowable limits The maximum allowable discharge per cycle Max Daily DoD MDDOD is 20 for Stand alone and 60 for Hybrid systems For discharge currents lower than 0 1 C10 the MDDOD is expressed in of the C10 value For example the cell RES 6 SOPzV 850 has C10 687Ah therefore a 60 MDDoD means 413 Ah extractable per day The maximum allowable DoD MDOD is 80 of the maximum availa...

Страница 5: ...r Connect the battery to the controller and leave it for 1 2 weeks while the application load is disconnected Full charge criteria are not applicable here Use the following voltage settings On off controllers 20 to 0 C 0 to 35 C 35 C High disconnect voltage Vr 2 55V 2 45V 2 40V Low restart voltage Vrr 2 35V 2 30V 2 25V Constant Voltage controllers 20 to 0 C 0 to 35 C 35 C Regulation voltage Vr 2 4...

Страница 6: ...over one month Controller type Setting 20 to 0 C 0 to 15 C 15 to 35 C 35 C Constant Voltage one step Vr 2 50V 2 45V 2 40V 2 35V Constant Voltage two steps absorption maximum 2 h per day 2 55V 2 50V 2 45V 2 40V float 2 45V 2 40V 2 35V 2 30V On off High voltage Vr 2 55V 2 50V 2 45V 2 40V Low voltage Vrr 2 35V 2 30V 2 30V 2 25V For systems with oversized PV array and low MDDOD 5 use lower settings se...

Страница 7: ... the minimum system voltage In Stand alone systems it is recommended to use controllers with adjustable LVD setting to the battery temperature higher LVD for lower temperature During operation the temperature difference between individual battery cells should be below 3o K 3 5 Current limits The maximum charging current during the bulk charging is 0 2 x C10 while the battery voltage is below the g...

Страница 8: ...m To avoid damage periodical equalizing charging see 3 2 1 or permanent float charging has to be made 8 Transport RES SOPzV cells are protected against short circuit If properly packed batteries are no dangerous goods according to the international regulations for dangerous goods on road and on rail ADR and RID Battery Voltage in relation to DoD as a guidance for the initial LVD settings first try...

Отзывы: