4 Electrical Connection
Quick User Manual
16
4.3.2 DC Cable Connection Procedures
Make sure that all the DC and AC cables to the inverter are not live before
you start the electrical work.
Neither the DC positive pole nor the DC negative pole of the PV string is
permitted to be grounded.
Step 1
Assemble the DC plug-in connectors and disconnect the DC switch.
Step 2
Check the connection cable of PV string for the correct polarity and that the
open-circuit voltage does not exceed the inverter input limit 1000V, even
under the lowest operating temperature.