System Decommissioning
8.1
Disconnecting the Inverter
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources.
Lethal voltages or damage to the inverter will follow if otherwise.
Step 1
Disconnect the external AC circuit breaker and secure it against reconnection.
Step 2
Rotate the DC switches to the “OFF” position for disconnecting all of the PV string
inputs .
Step 3
Wait about 5 minutes until the capacitors inside the inverter completely discharge.
Step 4
Ensure that the DC cable is current-free via a current clamp.
Step 5
Insert a PV terminal wrench into the notch and press the wrench with an appropriate
force to remove the DC connector.
Step 6
Ensure that the AC wiring terminals are voltage-free via a multimeter, and remove the
AC wires and communication wires.
Step 7
Install the PV terminal waterproof plugs.
For further disconnection and reconnection instructions, please visit the
webpage of respective component manufacturer.
-- -- E
En
nd
d
8.2
Dismantling the Inverter
Risk of burn injuries and electric shock!
•
Do not touch any inner live parts until at least 5 minutes after disconnecting
the inverter from the utility grid and the PV input.
Step 1
Refer to
for the inverter disconnection of all cables in reverse
steps.
Step 2
Dismantle the inverter referring to
in reverse steps.
Step 3
If necessary, remove the wall-mounting bracket from the wall.
Step 4
If the inverter will be reinstalled in the future, please refer to
for a
proper conservation.