8 Appendix
User Manual
38
Types
PVS-8M-HV
PVS-12M-HV
/PVS-16M-HV
Output cable
Type:50mm
2
Stranded
flame-retarded copper wire
Stripped length: 25mm
Bolt: M10
Tightening torque: 20N.m
Type:
70mm
2
/95mm
2
Stranded
flame-retarded
copper wire
Stripped length: 25mm
Bolt: M10
Tightening torque: 20N.m
Notice:
The withstanding voltage of the input and output cable must be
1500Vdc.
The copper cable is recommended for the PVS output terminal. If an
aluminum cable is selected, a copper aluminum terminal must be used
and the specification of the aluminum cable should meet the local
technical requirements.
Communicat
ion cable
Type: 2×1.5(4×1.5)mm
2
Four core STP with low resistance
Stripped length:7mm
Bolt: M3
Grounding
terminals
Type:16mm
2
Stranded flame-retarded copper wire
Stripped length: 15mm
Bolt: M6
Tightening torque:4N.m
8.3 Quality Assurance
Where any fault occurs during the warranty period, Sungrow will maintain or
replace the product for free.
Evidence
Sungrow Power Supply Co., Ltd. needs the users to provide the receipt invoice
and the date you purchase. Meanwhile the trademark should be clearly legible.
Otherwise Sungrow Power Supply Co., Ltd. has the right to exclude liability
claims.
Conditions
The original unqualified product should return to Sungrow.
Users should permit appropriate time to maintenance the device with fault for
Sungrow.
Exclusion of liability
Guarantee or liability claims for damages of any kind are excluded if they are
caused by one or more of the following: