Mechanical Mounting
Respect all local standards and requirements during mechanical installation.
4.1
Installation Location Selection
Selecting an optimal installation location for the Logger1000 is critical to safe operation, long
service life, and sound performance.
Take the following requirements into account when selecting the installation location:
•
With the ingress of protection IP20, the Logger1000 can be installed only indoors.
•
Ambient temperature range: -30
℃
to +60
℃
.
•
The relative humidity should not exceed 95%. If otherwise, the internal components will
be damaged.
•
Take anti-moisture and anti-corrosion measures.
•
Ensure that enough space is reserved around the Logger1000. The installation location
should be 1,500mm above the ground surface, and maintenance clearance of at least
500mm should be reserved. Minimum clearances are shown in the figure below.
When there are external devices (such as Meteo Station) connected to the
Logger1000, users should add corresponding communication SPD according to
onsite condition.