User Manual
2 LCD Operation
13
Parameter
Description
Default
Range
Lower PF Ind
Power factor of point P2 in the
Qp mode curve
0.900 0.9…1
Upper Power*
Output power of point P2 in
the Qp mode curve (in %)
100.0% 50%...100%
Lower Power*
Output power of point P1 in
the Qp mode curve (in %)
050.0% 0%...50%
Qu
Up U Limit
Grid voltage reference value 4
265.0 V
244 V...265 V
Low U Limit
Grid voltage reference value 1
207.0 V
-
U1 Limit
Grid voltage reference value 2
220.0 V
216 V... 230 V
U2 Limit
Grid voltage reference value 3
250.0 V
235 V... 255 V
Upper Q/Sn
Q/Sn value of voltage V1
30.0%
0%...60%
Lower Q/Sn
Q/Sn value of voltage V4
30.0%
0%...60%
*Lower Power <Upper Power
“
+”: the current leads the voltage, ”-”: the current lags the voltage”
Fig. 2-3
Reactive Power Regulation Curve in Q(p) Mode
Fig. 2-4
Reactive Power Regulation Curve in Q(U) Mode