background image

wiring should be bare or tinned copper, two conductor, 
stranded,  PVC  insulated,  with  a  PVC  UV  rated  jacket 
suitable for exterior use. In locations that often experi-
ence electrical storms and electrical atmospheric activi-
ty the low voltage sensor wire should also be shielded 
with the shielding grounded. 

Low  voltage  wire  shall  be  rated  for  the  full  ranges  of 
temperatures expected in the location, typically wire is 
rated  up  to  160

°

F.  The  low  voltage  sensor  wire  must 

not be in direct contact with the pipes as the wire insu-
lation  may  melt  when  in  contact  with  a  hot  pipe.  Low 
voltage sensor wire must be run OUTSIDE the pipe in-
sulation.  Where  the  low  voltage  wire  is  run  in  an  ex-
posed location, it should be run OUTSIDE the pipe insu-
lation but UNDER the insulation jacket or wrap to pro-
tect the wire from UV exposure. 

4.7 Installing the Solar tank 

The solar tank is heated indirectly through the external 
heat  exchanger  by  separate  pumps  on  the  collector 
loop and the potable side of the heat exchanger. 

When  plumbing  the  SunEarth  solar  storage  tank  and 
drainback reservoir make sure that all the components 
are  accessible  and  easy  to  reach.  Ensure  that  there  is 
clear  access  to  the  storage  tank,  circulating  pump, 
drainback reservoir, mixing valve, flow meter and other 
key components.  If a component in the potable water 
side  of  the  system  may  require  future  service  or 
maintenance  make  the  connections  with  brass  unions. 
Use  only  brass  nipples  and  unions  and  copper  and 
brass  fittings  in  plumbing  the  solar  storage  tank  and 
drainback  reservoir.    The  use  of  galvanized  fittings  or 
nipples, CPVC or PVC piping is prohibited. 

Check  valves  are  NOT  ALLOWED  anywhere  in  the  col-
lector loop.  A check valve in the collector loop will pre-
vent proper draining of the collectors and may result in 
freeze  damage.    If  the  pump  used  has  an  integral 
check  valve, the check  valve must be  removed before 

installing the pump in the system. 

Hard  copper  connections  to  the  city  cold  water  supply 
line  and  the  home  hot  water  feed  lines  are  recom-
mended.  The  gaskets  in  standard  water  heater  flex 
hose  connectors  can  become  brittle  and  compressed 
over  time  and  begin  leaking  on  the  water  heater.    If 
not  detected  in  a  timely  manner  even  a  small  drip  or 
leak may cause serious damage to the tank’s electrical 
components or, in extreme cases, may cause the tank 
to leak from the outside in. 

Tank plumbing is required to provide for the isolation of 
the solar storage tank  from the city cold water supply 
line by means of an isolating ball valve. 

The  differential  temperature  controller  shall  have  a 
screen  readout  to  show  temperatures  of  the  collector 
and  storage  tank.    Otherwise,  line  thermometers  shall 
be  installed  in  the  collector  supply  and  return  lines  to 
allow  for  a  simple  diagnostic  check  of  proper  system 
operation.    On  a  sunny  day  the  hot  water  return  line 
should be approximately 5 – 15°F warmer than the wa-
ter in the collector supply line.   

The specified SunEarth controller continuously displays 
the  temperature  of  the  SunEarth  collectors  (T1)  and 
the  temperature  at  the  bottom  of  the  solar  tank  (T2).  
In addition, you may choose to install a third tempera-
ture  sensor  (T3);  this  is  normally  installed  at  the  hot 
water outlet on both single and double tank systems.    

The Torrent Drainback system typically requires a high 
head,  low  flow  circulating  pump.    The  maximum  head 
on the pump curve must be greater than the static lift 
head required to fill the system.  The static lift head is 
the  vertical  height  from  the  bottom  of  the  drainback 
tank to the highest point in the system (usually the col-
lector outlet header).  When the pump is filling the sys-
tem it will be pumping against the static lift head and 
should  provide  no  less  than  0.5  GPM  flow.    Once  the 
system has been filled to the top of the collector, water 
will start to cascade down the return line filling the re-
turn  line  as  far  as  the  drainback  reservoir.    Once  this 
pipe is fully flooded the return line will start to siphon, 
resulting  in  an  increase  in  flow  as  the  system  transi-
tions from the filling condition to the running condition.  
In  the  running  condition  the  flow  rate  should  not  ex-
ceed  5  GPM.    Good  pump  selection  requires  that  the 
pump provide enough lift for the filling condition with-
out  excessive  flow  in  the  running  condition.    This  is 
usually  achieved  using  a  pump  with  a  “steep”  pump 
curve.    For  multistory  buildings,  this  can  be  especially 
challenging unless the drainback tank is located on the 
upper floor.  

When  there  is  a  risk  of  pump  cavitation  due  to  high 
flow rates, a pump throttling valve (COMPONENT #22) 
may be located on the discharge, or upstream, side of 
the pump to adjust the solar loop flow rate and to pre-
vent cavitation of the circulating pump.  Cavitation is a 
fluid condition that can lead to pitting or other damage 
to the pump impeller.  A throttling valve on the return 
piping from the collector to the drainback tank can also 

TANK SENSOR 

Fig.13 

THERMOWELL 

JIFFY CLIP (ALTERNATIVE) 

Содержание CASCADE 2

Страница 1: ...SRCC OG SRCC OG 300 Certified Solar Water Heating System 300 Certified Solar Water Heating System Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual ...

Страница 2: ...stem certification is granted to SunEarth by the SRCC It may not be used for any commercial purpose without prior written consent of SunEarth SunEarth must approve any deviation from the mate rials and methods described in this manual in writing The Cascade 2 Drainback solar water heating systems can be protected against freeze damage to temperatures as low as 50ºF 46ºC This system should not be i...

Страница 3: ... Isolation Procedures 14 8 Vacation procedures 14 9 Maintenance and Troubleshooting 14 10 Cascade 2 System Component Parts 15 11 Estimated Component Life 16 12 System Operating Parameters 16 Appendix A Approved Primary Components 18 Appendix C System and Component Labels 22 Appendix F SunEarth Collector Warranty Statement 24 Appendix G SRCC OG 300 Certified System Model Numbers 26 Appendix H Suppl...

Страница 4: ...ng to prevent con tact with HOT water NOTICE Mixing valves should be installed to reduce the point of use water temperature by mixing hot and col wa ter in branch water lines Contact a licensed installer or the local plumbing authority for further information The temperature of the water in the water heater can be regulat ed by setting the temperature dial of the adjustable surface mounted thermos...

Страница 5: ...cian or the local utility SAFETY PRECAUTIONS Have the installer show you the location of the circuit breaker and how to shut it off if necessary Turn off the circuit breaker if the water heater has been subjected to over heating fire flood or physical damage or if the ECO fails to shut off Read this manual entirely before in stalling or operating the water heating system Use this appliance only fo...

Страница 6: ...e fluid water in the collector array and solar loop piping drains back by gravity into the drainback storage reservoir when the pump stops circulating Air replaces water in the col lector array and solar loop piping to prevent it from freezing when the pump is off This manual is intended as a basic solar water heating primer Our goal is to familiarize you with the proper installation operation and...

Страница 7: ...r of any existing roof damage or necessary repairs 3 5 Structural Considerations The collectors must be located in a structurally sounds area of the roof Penetrations into structural members must not compromise the structural properties of the member ENSURE THAT ALL STRUCTURAL MEMBER PENE TRATIONS COMPLY WITH APPLICABLE CODES The collector mounting method must be capable of maintaining the require...

Страница 8: ...nEarth Solar Collector s 2 3 4 Temperature Sensor 5 6 7 8 22 Ball Valve 11 24 35 36 Combination Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temperature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 22 35 ROOF JACKS 36 ...

Страница 9: ...l Valve 11 24 35 36 Combina tion Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temper ature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 20 48 min T1 21 9 17 4 3 10 11 12 13 14 T3 PIPE INSULATION T2 22 24 23 25 35 ROOF JACKS 36 ...

Страница 10: ...25 1 SunEarth Solar Col lector s 2 3 4 Temperature Sensor 5 6 7 8 22 Ball Valve 11 24 35 36 Combina tion Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temper ature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 35 ROOF JACKS 36 ...

Страница 11: ...slope is 1 4 vertical drop per foot of horizontal piping run 2 minimum slope Use the steepest slope possible on the return line piping to the drainback reservoir Water will drain down both the return tubes directly to the drainback reservoir and the supply tubes by spinning the pump impeller in the re verse direction The collector should be mounted as close to the stor age tank as possible to mini...

Страница 12: ...tions The PEX tubing shall not be exposed to sunlight Water must be used as the heat transfer fluid The system shall be non pressurized capped at at mospheric on the day of installation or shall be vented to atmosphere A length of uninsulated copper tube no less than nominal diameter shall be used at the hot outlet and cold inlet of the solar collector s for a distance of no less than three feet 3...

Страница 13: ...e System out lined below All vertical piping between the storage tank and the collector shall be supported at each story or at maxi mum intervals of ten feet 10 Horizontal runs shall be sloped to drain minimum 2 slope and supported every five feet 5 to prevent sagging Roof runs shall be secured and supported providing at least 1 1 2 inches clearance from roof Pipe supports shall be con structed fr...

Страница 14: ...ector Sensor Placement The collector sensor shall be located on the solar loop return line as close to the collector as possible Sensors are typically accurate to 1 2 F if properly installed and weatherized The collector probe sensor shall be at tached to the SunEarth collector header pipe either with a stainless steel hose clamp or by inserting the probe sensor into a thermal well in contact with...

Страница 15: ...lumbing is required to provide for the isolation of the solar storage tank from the city cold water supply line by means of an isolating ball valve The differential temperature controller shall have a screen readout to show temperatures of the collector and storage tank Otherwise line thermometers shall be installed in the collector supply and return lines to allow for a simple diagnostic check of...

Страница 16: ... concrete slab in order to prevent moisture damage to the base of the tank and reduce the heat loss to the floor The tank should be raised off the floor on a pad 4 10 Choosing and Installing the Drainback Res ervoir SunEarth CopperStorTM copper drainback tanks are available in 2 5 5 7 5 and 10 gallon capacities Stain less steel drainback tanks are available in 10 15 and 20 gallons Small glass line...

Страница 17: ...illing the System Once the components have been plumbed it is time to fill the solar storage and collector loop with water as follows 4 14 1 STEP 1 Flush and Fill the potable loop with water Close potable flushing combination valves COMPONENTS 24 36 Fill the solar tank with wa ter and check that there are no leaks on the potable side of the system Do this by opening the cold water isolation ball v...

Страница 18: ...lso have been visual ly inspected for leaks and the solar loop piping has been cleaned and charged Having successfully com pleted these tasks it is time to set your system to run automatically Set the SunEarth control to the ON position Listen until you can hear water flowing through the solar loop return piping from the collector Place your ear next to the pump and listen for signs of cavitation ...

Страница 19: ...ons in excess of sixty days Remember to reset the SunEarth control to the AUTO position upon your return and check the system for proper operation and draining by monitoring the water levels with the pump on and off 9 MAINTENANCE AND TROUBLESHOOTING The following simple procedures are intended to opti mize the performance of your Torrent Drainback solar water heating system and also to extend the ...

Страница 20: ...e pump is running and the controller displays questiona ble temperatures at the collector or tank i e 180ºF tank and 45ºF collector check both sensors using a resistance meter to see if they are correctly calibrated If you find a defective sensor replace it immediately 9 10 Auxiliary Electric Element not Operating If the weather is poor and the auxiliary heating ele ment will not fire the bright r...

Страница 21: ...d by the plumbing code on water heaters Will automatically release and dump water at either 150 PSI of pressure or 210 F in temperature 21 Mixing Valve Automatically blends hot water from the solar storage tank with incoming city cold wa ter to an acceptable set point A mixing valve must be installed on every Torrent Drainback solar water heat ing system The mixing valve may include and integral c...

Страница 22: ...he system is not circulating pump stopped should such that the drainback tank not less than 75 full When the system is circulating pump running the water level in the drainback tank should be not less than 25 full The drainback tank should never be pumped dry in normal operation as this may result in damage to the circulator pump ...

Страница 23: ...pire Chrome EC 21 EC 24 EC 32 EC 40 EC 24 0 75 EC 32 0 75 EC 40 0 75 EC 24 1 5 EC 32 1 5 EC 40 1 5 SunEarth SunBelt SB 24 0 75 SB 32 0 75 SB 40 0 75 SunEarth Imperial Chrome IC 32 IC 40 SunEarth Imperial Selective IS 32 IS 40 SunEarth ThermoRay TRB 32 TRB 40 Make Series SunEarth SolarStrut RexRack Flush Mount Kit Universal Tilt Kit Landscape Rack Make Series Model Numbers SunEarth SunEarth SU80U 1...

Страница 24: ...ervoir Make Series Model Numbers AIC L Line LA14 10 Make Series Model Numbers SunEarth CopperStor DB 2 5 DB 5 DB 7 5 DB 10 SolarH2OT DBT DBT 10 SS DBT 15 SS DBT 20 SS Rheem Energy Miser 81VP6S 81VP15S 81VP10S 81VP20S A O Smith ProMax EJC 6 EJC 10 EJC 20 Or Approved Equal ...

Страница 25: ...e brass or stainless steel construction Maximum working temperature shall be no less than 200 F and maximum working pressure shall be no less than 125 psi Three Way Valves Optional Three Way valves shall be of bronze brass or stainless steel construction Maximum working tem perature shall be no less than 200 F and maximum working pressure shall be no less than 125 psi Boiler Drains A K A Charge Va...

Страница 26: ...rating tem perature of not less than 220o F and maximum working pressure of not less than 125 psi Pipe Insulation Pipe insulation shall have a maximum operating temperature of no less than 220o F All pipes shall be insulated to R2 6 or greater typically this will require a wall thickness of or greater When located in exposed areas pipe insulation shall be protected with a UV resistant coating or j...

Страница 27: ... WHENEVER THE CIRCULATION PUMP SHUTS OFF WHEN PROPERLY INSTALLED AND OPERATED THE SYSTEM IS PROTECTED TO TEMPERATURES AS LOW AS 50 F VALVE NO 8 COLD WATER SUPPLY ISOLATION VALVE THIS VALVE IS NORMALLY OPEN AND ALLOWS POTABLE WATER TO FILL THE SOLAR STORAGE TANK WHEN CLOSED THE SOLAR STORAGE TANK IS ISOLATED FROM THE PRESSURIZED CITY COLD WATER SUPPLY LINE PIPING BOILER DRAIN NO 11 SYSTEM FILL DRAI...

Страница 28: ...EED TO SOLAR TANK ISOLATION VALVE THIS VALVE IS NORMALLY OPEN WHEN CLOSED IN CONJUNCTION WITH VALVE NO 6 IT WILL ISOLATE THE SOLAR STORAGE TANK FROM THE POTABLE WATER SYSTEM VALVE NO 6 HOT OUTLET FROM SOLAR TANK ISOLATION VALVE THIS VALVE IS NORMALLY OPEN WHEN CLOSED IN CONJUNCTION WITH VALVE NO 7 IT WILL ISOLATE THE SOLAR STORAGE TANK FROM THE POTABLE WATER SYSTEM VALVE NO 5 SOLAR TANK BYPASS VAL...

Страница 29: ...APPENDIX F ...

Страница 30: ...APPENDIX F ...

Страница 31: ... 6 1 3 1 1 1 1 0 9 1 3 1 3 2 3 1 6 1 8 1 6 1 5 2 4 1 6 5 2 3 2 1 8 2 3 2 1 7 3 4 2 30004026 30004025 30004024 30004023 30004022 30004021 30004020 30004019 30004018 30004017 30004016 30004015 30004014 30004013 30004012 30004011 30004010 30004009 30004008 30004007 30004006 30004005 30004004 30004003 30004002 30004001 30004000 30003999 30003998 30003997 30003996 30003995 C2 80 120 TLG C2 64 120 TLG C...

Страница 32: ...________ System Information Model Number ___________________________________________ Date Purchased __________________________________________ Collector Serial Number ____________________________________ For Service and Repair Contact ______________________________ Comments ______________________________________________ ________________________________________________________ _____________________...

Страница 33: ...8425 Almeria Avenue Fontana CA 92335 Phone 909 434 3100 Fax 909 434 3101 Email info sunearthinc com www sunearthinc com Revised 3 17 2014 ...

Отзывы: