【M Series】Multi-turn Electric Valve Actuator
53
2021.06
Torque
:
After entering the end position range, the tripping torque will be set per the
setting value at “End Torque (Open)” and the actuator will stop running immediately
when the torque is higher than the setting value. Besides, the actuator will run to ful-
ly-open position (100%) when the torque is lower than setting value.
Default : Positon
Push Button
Function
Back to previous level to quit.
Switch menu item (up).
Switch menu item (down).
Save the change.
Set the CLOSE end position range and the setting range is from 2% to 20%.
After entering the end position range, the functions of the “Close End Stop Mod” and
“End Torque (Closed)” will be activate.
Default : 10%.
Push Button
Function
Back to previous level to quit.
Switch menu item (up).
Switch menu item (down).
Save the change.
Set the OPEN end position range, setting range is from 80% to 98%.
After entering the end position range, the functions of the “ Open End Stop Mod” and
“End Torque (Open)” will be activated.
Default : 90%.
[Close Position Range]
[Open Position Range]
Содержание M Series
Страница 1: ...SY04 C001A EN APP iOS Android ...
Страница 7: ... M Series Multi turn Electric Valve Actuator 4 2021 06 3 2 Nameplate Instruction Caution ...
Страница 24: ... M Series Multi turn Electric Valve Actuator 21 2021 06 Settings Menu 8 1 2 ...
Страница 25: ... M Series Multi turn Electric Valve Actuator 22 2021 06 ...
Страница 26: ... M Series Multi turn Electric Valve Actuator 23 2021 06 ...
Страница 75: ......