Sun StorEdge™ L25 Tape Library and Sun StorEdge™ L100 Tape Library Installation Guide
Document 6423015-01, Ver. 1, Rel. 0
June 2002
30
Connecting the Library to AC Power
Table 4 AC Distribution
Requirements, L25
# of
Library
Modules
Distribution Unit Requirements
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
1-2
Connect libraries to one AC distribution unit
rated minimum 10A, minimum 1.00mm2
<HAR> cord with minimum 10A plug. Must
be 3 wire grounding plug and wall outlet.
Connect libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG 3 wire cord, and a 15A or
20A plug. Must be 3 wire grounding plug and
wall outlet.
3-4
Select one of the following options:
• Connect no more than 2 libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm2 <HAR> cord with
minimum 10A plug. Must be 3 wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm2 <HAR> 3 wire cord with 3 wire
IEC60309 rated 16A. Must be 3 wire
grounding plug and wall outlet and have a
ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum 1.00
mm2 <HAR> 3 wire cord permanently
wired to the electrical supply. Must be
connected with a 3 wire cable and have a
ground warning label.
Connect libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG 3 wire cord, and a 15A or
20A plug. Must be 3 wire grounding plug and
wall outlet.