[23] ENA
default
When the automatic restart after overload is
enabled, if the output is turned off upon overload,
output is restarted by the mains after 3min delay.
The machine shall not restarted after 5 times of
restarts.
24
Automatic
restart after
overtemperat
ure
[24] DIS
When automatic restart after overtemperature
is disabled, if the output machine is turned off
upon overtemperature, no output is turned on.
[24] ENA
default
When automatic restart after overtemperature
is enabled, if the output is turned off upon
overtemperature, the output can be turned on
after the machine cools down.
25
Buzzer alarm
[25] DIS
Disabling alarm
[25] ENA
default
Enabling alarm
26
Mode
conversion
reminding
[26] DIS
No alarm prompt in case of any change in
main input source
[26] ENA
default
Alarm prompt is enabled if state of main input
source is changed.
27
Inverter
overload to
bypass
[27] DIS
No automatic switching to AC power in case
of inverter overload
[27] ENA
default
Automatic switching to AC power in case of
inverter overload
28
AC maximum
Charge current
[28] 40A
default
AC Out 120Vac Setting range 0~40A
29
Split Phase
[29] DIS
default
Supply for industrial frequency transformer
(disabled)
[29] ENA
Supply for industrial frequency transformer
(enabled)
30
RS485
Address setting
[30] 1
default
RS485 communication address setting range 1 ~
254, (refer to Number [32] is valid when set as SLA)
35
Battery
lowvoltage
recovery
[35] 52V
default
Setting range 44V~58.4V
37
Battery fully
charged
recovery point
[37] 52V
default
After the battery is fully charged, it needs to be
lower than this set voltage before it can be
recharged
38
AC output
Voltage setting
[38] 120Vac
default
Settable
:
(100/105/110Vac
)