5-2
Chapter 5
Precaution for using HF-TM2
5.3 List of affected parameter modes
Some functions of terminals become invalid when HF-TM2 is connected. Please confirm the parameters.
Code
Function name
Difference
dA-51
Input terminal monitor
Terminal [DFH] and [DHH] are always “L”.
dA-54
Output terminal monitor
No actual output from terminal [RL]
dA-70
Pulse train input monitor (internal)
Always 0.00%
AA101
Main speed input source selection, 1st-motor
Don’
t configure these parameters to“12
(Pulse train input (internal))” due to prevention the
malfunction.
AA102
Sub speed input source selection, 1st-motor
AA201
Main speed input source selection, 2nd-motor
AA202
Sub speed input source selection, 2nd-motor
Ad-01
Torque reference input source selection
Ad-11
Torque bias input source selection
Ad-40
Speed limit input source selection at torque control
AH-07
PID1 set-point 1 input source selection
AH-42
PID1 set-point 2 input source selection
AH-46
PID1 set-point 3 input source selection
AH-51
PID1 feedback 1 Input source selection
AH-52
PID1 feedback 2 Input source selection
AH-53
PID1 feedback 3 Input source selection
AJ-07
PID2 set-point input source selection
AJ-12
PID2 feedback input source selection
AJ-27
PID3 set-point input source selection
AJ-32
PID3 feedback input source selection
AJ-47
PID4 set-point input source selection
AJ-52
PID4 feedback input source selection
bA101
Upper frequency limit source selection, 1st-motor
bA201
Upper frequency limit source selection, 2nd-motor
CA-70
Frequency reference selection when [F-OP] is active.
CA-10
Input terminal [DFH] function
Don’t change these parameters due to prevention
the malfunction.
CA-11
Input terminal [DHH] function
CA-30
Input terminal [DFH] a/b(NO/NC) selection
CA-31
Input terminal [DHH] a/b(NO/NC) selection
CA-50
Input terminal [DFH] response time
Because there are no terminal for using these
functions, these parameters become invalid.
CA-51
Input terminal [DHH] response time
CA-81
Encoder constant setting
CA-82
Encoder phase sequence selection
CA-83
Motor gear ratio numerator
CA-84
Motor gear ratio denominator
CA-90
Pulse train input, target function selection
CA-91
Pulse train input mode selection
CA-92
Pulse train frequency scale
CA-93
Pulse train frequency filter time constant
CA-94
Pulse train frequency bias size
CA-95
Pulse train upper frequency detection level
CA-96
Pulse train lower frequency detection level
CA-97
Pulse counter compare match output ON value
CA-98
Pulse counter compare match output OFF value
CA-99
Pulse counter maximum value
CC-06
Output terminal [RL] function
No actual output, but monitoring is possible (dA-54).
CC-16
Output terminal [RL] active state
Because there are no terminal for using these
functions, these parameters become invalid.
CC-30
Output terminal [RL] on-delay time
CC-31
Output terminal [RL] off-delay
CC-01 to
CC-05
CC-07
Output terminal [ * ] function
* = UPF to X3, FL
Because there are no terminals for using the below
function, the setting to these parameters become
invalid. 044: Pulse count compare-match output