Section 5
CONTROLLER
25
CLASS
SD/WA
EMS DISPLAY
SET POINT
B
WA
CAT ECM DIAGNSTC
ON
A
SD
CAT SD
ON
S
SD
C267 COMM FAIL
lost signal
S
SD
MDDM COMM FAIL
lost signal
A
SD
LST ANLG P1 SD
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
A
SD
LST ANLG P2 SD
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
A
SD
LST ANLG P3 SD
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
A
SD
LST ANLG P4 SD
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
A
SD
LST ANLG T1 SD
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
A
SD
LST ANLG T2 SD
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
A
SD
LST ANLG T3 SD
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
A
SD
LST ANLG T4 SD
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
S
AL
S #1 COM
slave #1 communication failure
S
AL
S #2 COM
slave #2 communication failure
S
AL
S #3COM
slave #3 communication failure
S
AL
S #4 COM
slave #4 communication failure
S
AL
S #5 COM
slave #5 communication failure
S
AL
S #6 COM
slave #6 communication failure
S
AL
S #7 COM
slave #7 communication failure
S
AL
S #8 COM
slave #8 communication failure
S
AL
S #9 COM
slave #9 communication failure
“A”
always armed
“B”
armed when the lockout delay timer expires
“S”
armed when its own lockout delay timer expires
When a shutdown or warning condition exists, the reset button must be pressed to clear and reset the system.
In the case of a warning, when the reset push button is pressed, if the warning condition has already cleared
itself, then the warning display and compressor warning/shutdown light will be cleared. If the warning condi-
tion is still present, then the warning display and the compressor warning /shutdown light will remain on. In
the case of a shutdown, the unit will be locked out from running or being restarted until the reset push button
is pressed. Once the reset push button is pressed, and the shutdown condition has been cleared, the com-
pressor warning/shutdown light will be turned off, and the unit will go into “STANDBY” mode to be ready to
start.
Table 5-2 Controller Responses
Содержание DE-18
Страница 6: ...NOTES...
Страница 14: ...8 NOTES...
Страница 18: ...12 NOTES...
Страница 23: ...Section 4 COMPRESSOR SYSTEMS 17 Figure 4 4 Piping and Instrumentation Diagram...
Страница 25: ...19 NOTES...
Страница 26: ...Section 5 CONTROLLER 20 Figure 5 1 Control Panel...
Страница 32: ...26 NOTES...
Страница 36: ...30 NOTES...
Страница 51: ...45 NOTES...