SECTION 2
PRODUCT USER MANUAL
11
2.7
INSTALLATION LAYOUT
REQUIREMENTS
1. The dryer must be installed horizontally. A
minimum of at least 1.5 feet / 0.5 meters
clearance around the dryer is necessary to
allow free air circulation and easy access for
servicing.
2. The ambient temperature in the room should
not exceed 120°F / 49°C and should not be
below 40°F / 4°C, taking into account the
heat radiated by the dryer. (About 18 watts
for each SCFM under ISO 7183-5 condition
or 40 watt for each liter/sec under ISO 7183-
A condition).
2.8
ENVIRONMENTAL
PROTECTION
1. US/EU laws protect the environment against
refrigerant being released into the atmo-
sphere.
2. An annual leak control test at less than 5.0
gr/year should be performed by a qualified
engineer if the refrigerant dryer contains
more than 4.4 lbs / 2 kg of refrigerant. This
control test has to be done twice a year if the
dryer contains more than 66 lbs / 30 kg.
3. Prior to dryer disposal, the refrigerant must
be properly recovered by a qualified engi-
neer.
2.9
PRODUCT DESCRIPTION
This refrigerated compressed air dryer has been
designed to remove water vapor from industrial
compressed air that is free of any aggressive
contaminants like ammonia, gaseous acid, dust, rust,
liquid condensate, any other chemical or mineral
substances capable of attacking or clogging the heat
exchanger(s).
The optional, water-cooled condenser is not
designed for use with seawater or water containing
aggressive contaminants.
Please contact your factory representative for further
questions on this issue. This dryer has been
designed for indoor operation only.
The minimum and maximum values stated must be
observed, as well as the safety precautions
described in this manual.
2.10 PRODUCT FEATURES
2.10.1 R
EFRIGERANT
COMPRESSOR
The refrigerant compressor is fully hermetically
sealed and requires no maintenance.
2.10.2 C
ONDENSER
1. Air cooled models: The refrigerant con-
denser is equipped with fans that are cycled
on and off to maintain a minimum high side
pressure.
2. Water-cooled dryers Utilize a water control
valve piloted by a sensing bulb that reacts to
the high side refrigerant pressure controlling
the water flow Maintain a minimum high side
pressure.
2.10.3 R
EFRIGERANT
CIRCUIT
PROTECTION
1.
High/Low pressure safety switch
:
Refrigerant circuits are protected against
excessive pressure by a safety switch that
stops the compressor in cases of high or low
refrigerant pressure. If this safety switch has
tripped out on high refrigerant pressure, it
has to be manually reset before the dryer
can be restarted. A low pressure trip will
automatically reset.
2.10.4 F
ILTER
D
RIER
Total water removal in the refrigerant circuit is
achieved by a filter drier who also traps any solid
particles that may have migrated into the circuit
during assembly.
2.10.5 C
RANKCASE
HEATER
3-Phase dryers are equipped with an electric
crankcase heater. The heater provides preliminary
pre-heating of the refrigerant compressor to
evaporate liquid refrigerant possibly condensed in
the crankcase. This will prevent liquid shock that can
Содержание 02250201-297 R01
Страница 6: ...TABLE OF CONTENTS ...
Страница 8: ...8 NOTES ...
Страница 38: ...38 NOTES ...
Страница 39: ...Section 4 39 TECHNICAL DRAWINGS ...
Страница 40: ...SECTION 4 40 4 1 ED SPARE PARTS RD400 AIR COOLED 02250196 586 R03 ...
Страница 42: ...SECTION 4 42 4 2 ED SPARE PARTS RD500 AIR COOLED 02250196 588 R03 ...
Страница 44: ...SECTION 4 44 4 3 ED SPARE PARTS RD700 AIR COOLED 02250196 590 R3 ...
Страница 46: ...SECTION 4 46 4 4 ED SPARE PARTS RD700 WATER COOLED 02250196 618 R03 ...
Страница 48: ...SECTION 4 48 4 5 ED SPARE PARTS RD850 AIR COOLED 02250196 591 R03 ...
Страница 50: ...SECTION 4 50 4 6 ED SPARE PARTS RD850 WATER COOLED 02250196 619 R03 ...
Страница 52: ...SECTION 4 52 4 7 ED SPARE PARTS RD1000 AIR COOLED 02250196 592 R03 ...
Страница 54: ...SECTION 4 54 4 8 ED SPARE PARTS RD1000 WATER COOLED 02250196 620 R03 ...
Страница 56: ...SECTION 4 56 4 9 ED SPARE PARTS RD1200 AIR COOLED 02250196 593 R03 ...
Страница 58: ...SECTION 4 58 4 10 ED SPARE PARTS RD1200 WATER COOLED 02250196 621 R03 ...
Страница 60: ...SECTION 4 60 4 11 ED SPARE PARTS RD1600 AIR COOLED 02250196 594 R03 ...
Страница 62: ...SECTION 4 62 4 12 ED SPARE PARTS RD1600 WATER COOLED 02250196 622 R03 ...
Страница 64: ...SECTION 4 64 4 13 ED SPARE PARTS RD2000 AIR COOLED 02250196 595 R03 ...
Страница 66: ...SECTION 4 66 4 14 ED SPARE PARTS RD2000 WATER COOLED 02250196 623 R03 ...
Страница 68: ...SECTION 4 68 4 15 ED SPARE PARTS RD2400 AIR COOLED 02250196 596 R03 ...
Страница 70: ...SECTION 4 70 4 16 ED SPARE PARTS RD2400 WATER COOLED 02250196 624 R03 ...
Страница 72: ...SECTION 4 72 4 17 ED SPARE PARTS RD3000 AIR COOLED 02250196 597 R03 ...
Страница 74: ...SECTION 4 74 4 18 ED SPARE PARTS RD3000 WATER COOLED 02250196 625 R03 ...
Страница 76: ...SECTION 4 76 4 19 ED SPARE PARTS RD3800 AIR COOLED 02250196 598 R03 ...
Страница 78: ...SECTION 4 78 4 20 ED SPARE PARTS RD3800 WATER COOLED 02250196 626 R03 ...
Страница 80: ...SECTION 4 80 4 21 ED SPARE PARTS RD5000 AIR COOLED 02250196 599 R03 ...
Страница 82: ...SECTION 4 82 4 22 ED SPARE PARTS RD5000 WATER COOLED 02250196 627 R03 ...
Страница 84: ...SECTION 4 84 4 23 ED SPARE PARTS RD6000 AIR COOLED 02250196 600 R03 ...
Страница 86: ...SECTION 4 86 4 24 ED SPARE PARTS RD6000 WATER COOLED 02250196 628 R03 ...
Страница 88: ...SECTION 4 88 4 25 ID RD400 02250195 264 ...
Страница 89: ...SECTION 4 89 4 25 ID RD400 DRYER WITHOUT PALLET SIZE RD 400 23 23 x 27 95 x 49 8 590mm x 710mm x 12651270mm ...
Страница 90: ...SECTION 4 90 4 26 ID RD500 850 02250195 266 ...
Страница 92: ...SECTION 4 92 4 27 ID RD1000 1200 02250195 267 R01 ...
Страница 94: ...SECTION 4 94 4 28 ID RD1600 2000 02250195 268 ...
Страница 96: ...SECTION 4 96 4 29 ID RD2400 02250195 269 ...
Страница 98: ...SECTION 4 98 4 30 ID RD3000 02250195 269 ...
Страница 100: ...SECTION 4 100 4 31 ID RD3800 02250195 270 ...
Страница 102: ...SECTION 4 102 4 32 ID RD5000 02250195 271 ...
Страница 104: ...SECTION 4 104 4 33 ID RD6000 02250195 272 ...
Страница 106: ...SECTION 4 106 4 34 P I RD400 02250195 291 ...
Страница 108: ...SECTION 4 108 4 35 P I RD500 850 02250195 293 ...
Страница 110: ...SECTION 4 110 4 36 P I RD700 850 WATER COOLED 02250195 294 ...
Страница 112: ...SECTION 4 112 4 37 P I RD1000 6000 02250195 297 ...
Страница 114: ...SECTION 4 114 4 38 P I RD1000 6000 WATER COOLED 02250195 298 ...
Страница 116: ...SECTION 4 116 4 39 WIRING DIAGRAM RD400 230 3 60 A 02250195 319 S1 ...
Страница 118: ...SECTION 4 118 4 39 WIRING DIAGRAM RD400 230 3 60 A 02250195 319 S2 ...
Страница 120: ...SECTION 4 120 4 40 WIRING DIAGRAM RD400 460 3 60 A 400 3 50 A 02250195 974 S1 ...
Страница 122: ...SECTION 4 122 4 40 WIRING DIAGRAM RD400 460 3 60 A 400 3 50 A 02250195 974 S2 ...
Страница 124: ...SECTION 4 124 4 41 WIRING DIAGRAM RD500 700 230 3 60 A 02250195 975 S1 ...
Страница 126: ...SECTION 4 126 4 41 WIRING DIAGRAM RD500 700 230 3 60 A 02250195 975 S2 ...
Страница 132: ...SECTION 4 132 4 43 WIRING DIAGRAM RD700 850 230 3 60 W 02250195 976 S1 ...
Страница 134: ...SECTION 4 134 4 43 WIRING DIAGRAM RD700 850 230 3 60 W 02250195 976 S2 ...
Страница 140: ...SECTION 4 140 4 45 CONTROL CIRCUIT RD400 500 700 850 1000 1200 1600 2000 2400 3000 3800 5000 6000 02250195 307 ...
Страница 142: ...SECTION 4 142 4 46 POWER CIRCUIT RD400 500 700 850 1000 1200 1600 2000 2400 3000 3800 5000 6000 02250195 307 ...
Страница 144: ...144 NOTES ...
Страница 145: ...NOTES ...