Sub-Zero SZ-7552-P Скачать руководство пользователя страница 3

12

This mode is used to set the time 
delay between the switching off 
of both compressors so that they 
do not switch off simultaneously. 

Example :

 If this mode is set to 

3 seconds the second compressor 
will switch off after a minimum 
of 3 seconds from the first 
compressor switching off. 

If set to 0, this feature will not 
activate. 

Function : To set minimum off 
time between two compressor.

To change 
t3 parameter, 
press the 
SET key.

t3 
Parameter

Max Fac.

5 Sec

15 Sec

Min

0 Sec

13

To change 
t4 parameter,
press the
SET key.

This function is used to avoid 
overloading  of  any one compressor 
working at a stretch over a period of 
time. 

Example :

 If this parameter is set at 

2 hours, the setpoint, differential & 
time delay of both compressors will 
interchange after 2 hours The 
interchange will occur every 2 hours. 

Time calculation will start at power on. 
This helps by not overworking any 
one compressor for long hours and
increases compressor life. If for any 
reason the setpoints have been 
changed, the time calculation will   
start from the last change in these 
parameters.  

Function : To avoid overloading of 
either compressor. 

t4
Parameter

Max Fac.

0 Hr

12 Hrs

Min

0 Hr

15

When display
shows E1 press
SET key.

Use UP/DOWN keys to set 
desired value.

0 =  Both the relays will 
      stay on with initial start-up 
      delay of 2 minutes.

1 =  Both compressor
      performs a duty cycle of 
     10 minutes ON and 
      4 minutes OFF.

2 =  Both relay will stay OFF.

Function : Relay status on probe
failure.

E1 
Parameter

Max Fac.

1

2

Min

14

LP 
Parameter

Function: To Lock keypad.

To change 
LP parameter, 
press the
SET key.

Use UP/DOWN keys to set desired 
value. This parameter can lock the 
keypad so that tampering is not 
possible by by-standards.

0 = Keypad unlocked.
1 = Keypad locked.

When locked all parameters can 
only be viewed, but not modified.

Max Fac.

0

1

Min

0

16

rS 
Parameter

Function: To set controller Resolution.

To change 
rS parameter
press the
SET key.

Use UP/DOWN keys to set desired 
value.

1 = Controller Resolution will 

O

      set 0.1 C.

0 = Controller Resolution will 

O

      set 1 C.

Max Fac.

0

1

Min

0

11

If set to 0, this feature will not activate.

Example  :

  If  setpoint  1  is  23  and 

setpoint 2 is 25 and if t2 para is set to 7 
minutes, if the second comp. cuts out 
at 25, if comp. 1 is not able to achieve 
23 for a period of 7 minutes, then after 
7  minutes,  second  compressor  will 
also  come  on  and  both  compressors 
will cutout at the lower setpoint.

This  function  is  used  to  switch  on 
the  second  compressor  incase 
the  heat  load  cannot  be  met  with 
one compressor functioning.

If t2 is set less than P6, then P6 para
will override t2 parameter.

Function : To start second comp. incase 
comp  1  cannot  achieve  the  lower  set 
point.

To change 
t2 parameter, 
press the
SET key.

t2 
Parameter 

Fac.

0 Min

Max

30 Min

Min 

0 Min

NOTE  :  T2  parameter  is  activated 
only when P1=0 (cooling).