      R1 & time delay of setpoint 1 
will flash. Use UP/DOWN keys to set
desired value. Once desired value is 
achieved, press set key and you will 
see “- - -” which confirms time delay for
set point 1 has been stored in memory.

After pressing UP key      R2 flashes 
alongwith the time delay for setpoint 2. 
Use UP/DOWN keys to set desired,
value.Once desired value is
achieved, press set key and you will 
see “- - -” which confirms time delay for
set point 2 has been stored in memory.

To prevent both compressors from 
switching on together, there is an 
internal 10 second time delay 
between simultaneous startups 
to prevent an electrical surge.

Function : Set time delay between relay 
restart time for comp1 and comp2.

To change 
P6 parameter, 
press the 
SET key.

Time delay R1

Time delay R2

P6 
Parameter 

Fac.

3 Min

Max

20 Min

Min 

0 Min

Fac.

3 Min

Max

20 Min

Min 

0 Min

R1

R2

8

P4 
Parameter 

   

Once in this mode,    R1 and 
differential of setpoint 1 will flash.
use UP/DOWN keys to set desired 
value. Once desired value is achieved, 

   

press set key and you will see “- - -” this
confirms differential for set point 1 has 
been stored.

After up key is pressed  
     R2 flashes alongwith the differential 
for set point 2. Use UP/DOWN keys to 
set desired value. Once value is 
achieved, press set key. This confirms 
differential for setpoint 2.

0

Example 

: If setpoint 1 is set at 10.0

C.

and differential for setpoint 1 is set

0

at 2.0 C, then when the system 

0

reaches 10.0 C, the relay for 
compressor 1 will cutout and since 

O

the differential is 2.0 C the relay will 

O

cutin(restart) at 12.0 C (10.0+2.0).

Function: To set the differential of 
set point 1 and set point 2

To change 
P4 parameter, 
press the
SET key.

Differential 1 & 2

Differential 1  & 2

Max Fac.

0

20.0 C

0

0.5 C

Min 

0

2.0 C

Max Fac.

0

20 C

0

1 C

Min 

0

2 C

rS = 0

rS = 1

rS = Resolution 

Set Parameter

9

Use UP/DOWN keys to set 
desired value. In time it may be 
possible that the display may be 
offset by a degree or so.  

To compensate for this error. you 
may need to add or minus the degree
required to achieve the correct 
temperature. Setting value is from 

O

O

-10.0 C to + 10.0 C.

Example :

 The temperature on the 

O

display is 28.0 C, whereas the actual

O

temperature is 30.0 C. You will need 
to set the P5 mode to 2.0, which 
mean that once out of the 
programming mode, the display 

O

will show temperature 30.0 C 

O

O

(28.0 C + 2.0 C).

To change 
P5 parameter 
press the
SET key.

Function : To set probe calibration.

P5
Parameter 

Max Fac.

0

10.0 C

0

-9.0 C

Min 

0

0.0 C

rS = 0

Max Fac.

0

10 C

0

-9 C

Min 

0

0 C

rS = 1

rS = Resolution 

Set Parameter

6

Function : To set maximum 
allowable high temperature limit. 

To change 
P2 parameter,
Press the
SET key.

Use UP/DOWN key to set 
desired value. Once set at a 
particular value, this will not 
allow both set points to go above 
this value

.

Example : 

Setting this parameter 

0

at 30.0 C will not allow both set 

0

points to go above 30.0 C. Also if 

0

the temperature reaches 30.0 C, the 
display will show Ht (High
Temperature), indicating that the 
temperature has reached or gone 
above the value in this 
parameter.  

XX = Highest Set Point

(Message on Display)

P2 
Parameter 

Max

Max

Fac.

Fac.

0

50.0 C

0

50 C

Min 

Min 

0

XX+1 C

0

50.0 C

0

50 C

rS = 0

rS = 1

rS = Resolution 

Set Parameter

XX

0

+1.0 C

7

To change 
P3 parameter, 
press the
SET key. 

Use UP/DOWN key to set 
desired value. Once set at a 
particular value, this will not 
allow both set points to go below 
this value

.

Example :

 Setting this parameter 

0

at 10.0 C will not allow both set 

0

points to go below 10.0 C. Also if 

0

the temperature reaches 10.0 C, the 
display will show Lt (Low
Temperature), indicating that the 
temperature has reached or gone 
below the value in this 
parameter.  

Function : To set minimum 
allowable low temperature limit. 

(Message on Display)

P3 
Parameter 

XX = Lowest Set Point

0

0.0 C

0

0.0 C

Max Fac.

Min 

rS = 0

0

XX-1 C

Max Fac.

0

0 C

0

0 C

Min 

rS = 1

rS = Resolution 

Set Parameter

XX

0

-1.0 C

5

P1 Parameter

Function: To set controller for heating 
or cooling.

0

1

0

To change
the P1
parameter,
press the
SET key.

Use UP/DOWN keys to get
desired value & press set
to confirm.
0: Cooling mode and 
1: Heating mode.

Min

Max

Fac.

NOTE : T2 parameter is activated 
only when P1=0 (cooling).