Description of parameters and functions.
Parameter setting
method.
AFT PROBE STATUS
LOW TEMP ALARM
Use UP/DOWN keys to set desired value.
Disable = It disables the Antifreeze Trip
function of the controller.
Enable = It enables the Antifreeze Trip
function of the controller.
Use UP/DOWN keys to set desired
value.
SET = Chiller Set Temperature.
AFT = AFT Set Temperature.
EXAMPLE :
Setting this parameter at
0
15.0 C will not allow the set point to go
0
below 15.0 C Also, if the temperature
0
reaches or goes below 15.0 C the
display will show Low Temp. Alarm and
at this point the alarm will activate.
To change AFT PROBE
STATUS parameter, press the
set key.
To change Low Temp Alarm
Parameter, press the set key.
10
09
Range
Range
Min
Min
Max
Max
Fact. Set
Fact. Set
Function: To enable or disable Antifreeze
function.
Function: To set minimum allowable low
temperature limit and alarm.
0 Min
20 Min
1 Min
Disable
+1.0ºC
AFT
Enable
SET-0.5ºC
Disable
6.0ºC
HT PWR ON DLY
08
Function: To set Power on delay for Ht
alarm.
To change Ht Pwr On Delay.
parameter,press the set key.
Example :
If this parameter is set to 20
Min, once the unit is powered on the Ht
alarm will not activate for 20 minutes even
if there is a fault. This is very useful to
eliminate the nuisance alarm when a unit
is switched on.
Use UP/DOWN keys to set desired value.
This parameter sets a time delay on
power on for the Ht alarm.
8
7
Sr.No.
Parameter
(LCD Message)
Description of parameters and functions.
Parameter setting
method.
1.0ºC
10.0ºC
2.0ºC
EXAMPLE :
If this parameter is set at 3
minutes, the compressor will cut off at the
set temperature, but will not restart for a
minimum of 3 minutes. This time delay is
also effective at 'Power On’
of the system.
This safety feature is used to protect the
compressor from restarting within a short
period due to power fluctuations.
Range
Min
Max
Fact. Set
0 Min
20 Min
3 Min
0
EXAMPLE :
If the set point is setat 10.0 C
0
and differential is set as 2.0 C, then when
0
t h e s y s t e m r e a c h e s 1 0 . 0 C , t h e
compressor will cutoff. Since differential
0
is 2.0 C, the compressor will cut in(restart)
0
0
0
at 12.0 C (10.0 C + 2.0 C).(Cooling Mode)
Use UP/DOWN keys to set desired value.
To change
DIFFERENTIAL
parameter,press the set key.
06
Range
Min
Max
Fact. Set
DIFFERENTIAL
Function: To set temperature differential
for compressor restart.
HIGH TEMP. ALARM
SET = Chiller Set Temperature.
Use UP/DOWN keys to set desired value.
Once set at a particular value, this will not
allow the set point to go above this value
and below Low Temp Alarm setting.
EXAMPLE :
Setting this parameter at
0
25.0 C will not allow the set point to go
0
above 25.0 C. Also if the temperature
0
reaches or goes above 25.0 C the display
will show High Temp. Alarm & at this point
the alarm will activate.
To change HI Temp Alarm
parameter,press the set key.
07
Range
Min
Max
Fact. Set
Function: To set maximum allowable high
temperature limit and alarm.
SET
O
+0.5 C
70.0ºC
50.0ºC
05
COMP. TIME DELAY
Function : To set compressor restart
delay.
Use UP/DOWN keys to set desired value.
parameter,press the set key.
To change Comp Time Delay