AFT PROBE STATUS

LOW TEMP ALARM

Use UP/DOWN keys to set desired value. 

Disable  = It disables the Antifreeze Trip  
                function of the controller.
Enable  = It enables the Antifreeze Trip 
                function of the controller.

Use UP/DOWN keys to set desired 
value. 

SET = Chiller Set Temperature.
AFT = AFT Set Temperature.

EXAMPLE : 

Setting this parameter at 

0

15.0 C  will not allow the set point to go 

0

below 15.0 C Also, if the temperature 

0

reaches or goes below 15.0 C  the 

 

display will show Low Temp. Alarm and 
at this point the alarm will activate.

To change AFT PROBE 
STATUS parameter, press the 
set key.

To change Low Temp Alarm 
Parameter, press the set key.

10

09

Range

Range

Min 

Min 

Max 

Max 

   Fact. Set 

   Fact. Set 

Function: To enable or disable Antifreeze  
function.

Function: To  set  minimum  allowable  low 
temperature limit and alarm.

0 Min

20 Min

1 Min

Disable

+1.0ºC

AFT

Enable 

SET-0.5ºC

Disable

6.0ºC

HT PWR ON DLY

08

Function: To set Power on delay for Ht 
alarm.

To change Ht Pwr On Delay.
parameter,press the set key.

Example : 

If this parameter is set to 20 

Min, once the unit is    powered on the Ht 
alarm will not activate for 20 minutes even 
if  there  is  a  fault.  This  is  very  useful  to 
eliminate the nuisance alarm when a unit 
is switched on.

Use UP/DOWN keys to set desired value. 

This  parameter  sets  a  time  delay  on 
power on for the Ht alarm.

8

7

Sr.No. 

Parameter 

(LCD Message)

Description of parameters and functions.

Parameter setting

 method. 

1.0ºC

10.0ºC

2.0ºC

EXAMPLE :

 If this parameter is set at 3 

minutes, the compressor will cut off at the 
set temperature, but will not restart for a

 

minimum of 3 minutes. This time delay is 
also effective at 'Power On’

 

of the system. 

This safety feature is used to protect the 
compressor from restarting within a short 
period due to power fluctuations.

Range

Min 

Max 

   Fact. Set 

0 Min

20 Min

3 Min

 

0

EXAMPLE :

 If the set point is setat 10.0 C 

 

0

and differential is set as 2.0 C, then when 

0

 

t h e   s y s t e m   r e a c h e s   1 0 . 0 C , t h e

 

compressor   will cutoff. Since differential 

0

  

 

is 2.0 C, the compressor will cut in(restart) 

0

0

0

at 12.0 C (10.0 C + 2.0 C).(Cooling Mode)

Use UP/DOWN keys to set desired value.

To change 

DIFFERENTIAL 

parameter,press the set key.

06

Range

Min 

Max 

   Fact. Set 

DIFFERENTIAL 

Function: To set temperature differential 
for compressor restart.

HIGH TEMP. ALARM

SET = Chiller Set Temperature.

Use UP/DOWN keys to set desired value. 
Once set at a particular value, this will not 
allow the set point to go above this value 
and below Low Temp Alarm setting.

EXAMPLE  : 

Setting  this  parameter  at 

0

25.0 C  will  not  allow  the  set  point  to  go 

0

 

above  25.0 C. Also  if  the  temperature 

0

 

reaches or goes above 25.0 C the display 
will show High Temp. Alarm & at this point 
the alarm will activate.

To change HI Temp Alarm
parameter,press the set key.

07

Range

Min 

Max 

   Fact. Set 

Function: To set maximum allowable high 
temperature limit and alarm.

SET

O

+0.5 C

70.0ºC

50.0ºC

05

COMP. TIME DELAY

Function  :  To  set  compressor  restart 
delay.

Use UP/DOWN keys to set desired value.

parameter,press the set key.

To change Comp Time Delay

Содержание MICRO CHILL

Страница 1: ...www pvrcontrols com INDIA...

Страница 2: ...nical Data 15 Suggested Wiring Diagram 16 Panel Cutout Dimensions 17 2 LIQ LEVEL FAULT To set liquid level fault on high level or low level 12 1 Index Index Introduction Get to Know Your Controller Pa...

Страница 3: ...on for Compressor FEATURES The MICRO CHILL is a Single compressor chiller controller This integrates all the required functions of the chiller It is very user friendly due to the LCD provided which gi...

Страница 4: ...arameter setting method 01 Press and hold set key for 2 seconds and release Range Min Max Fact Set Lt 0 5 C Ht 0 5 C 10 0 C PROGRAM MODE To set other parameters Hold key for 2 seconds and release LCD...

Страница 5: ...age Description of parameters and functions Parameter setting method 1 0 C 10 0 C 2 0 C EXAMPLE If this parameter is set at 3 minutes the compressor will cut off at the set temperature but will not re...

Страница 6: ...0 C 10 0 C 0 0 C 9 Sr No Parameter LCD Message Description of parameters and functions Parameter setting method AFT SET TEMP Use UP DOWN keys to set desired value To change AFT SET TEMP parameter pres...

Страница 7: ...On With Comp With Comp PUMP RUN LOGIC Use UP DOWN keys to set desired value With Pump In this case pump will switch Always On It sets the pump to always on mode On and off with compressor Parameter pr...

Страница 8: ...e Parameter press the set key 32 Function To end programming 13 Sr No Parameter LCD Message Description of parameters and functions Parameter setting method RELAY3 LOGIC Use UP DOWN keys to set desire...

Страница 9: ...Panel Cutout 91 X 91 MM ALL Relay 5A 250VAC 2 5 sq mm one wire terminal only O O Range 30 C to 70 C Data storage Non volatile EEPROM memory Digital Input Potential 230Vac O O Probe tolerance at 25 C 0...

Страница 10: ...on water and corrosive gasses and where ambient temperature does not exceed the values specified in the technical data Probe To give a correct reading the probe must be installed in a place protected...

Страница 11: ...e purchase of this product 19 Specifications are subject to change due to continuous improvements of our products No consequential damage or field labour is included in the sales of products mentioned...

Отзывы: