R3
Set point for compressor3
U
R4
R3
7.5
o
C
0.5
R4
Differential for compressor1
U
1.0
10.0
2.0
o
C
0.5
R5
Differential for compressor2
U
1.0
10.0
2.0
o
C
0.5
R6
Differential for compressor3
U
1.0
10.0
2.0
o
C
0.5
R7
Maximum Cooling Setpoint
Once set at a particular range, this will not
allow the set point to go above this range and
below R4 setting.
Example: Setting this parameter at 25
0
Cwill
not allow the set point to go above 25
0
C.
Also if the temperature reaches 25
0
C the
display will show Ht (High Temp)
indicating that the temperature has gone
above the range in this parameter and at this
point the alarm will come on.
F
R6
50
50
o
C
0.5
R8
Minimum Cooling Setpoint
Use UP/DOWN keys to get desired range &
press set key to confirm.
Once set at a particular range, this will not
allow the set point to go below this range and
above R3 setting
Example: Setting this parameter at -30
0
C
will not allow the set point to go below
-30
0
C. Also if the temperature reaches -30
0
C
the display will show Lt (Low Temp)
indicating that the temperature has gone
below the range in this parameter and at this
point the alarm will come on.
F
-30
R5
-30
o
C
0.5
C1
Time delay for compressor1 restart
E.g. If this parameter is set at 3MIN,then
after cutting off the compresso1r at set
temperature compressor1 will not
Restart for a minimum of 3min.This time
delay is also active at power on of the system
.
F
0
20
3
Min
1
C2
Time delay for compressor2 restart
E.g. If this parameter is set at 3MIN,then
after cutting off the compressor2 at set
temperature compressor2 will not
Restart for a minimum of 3min.This time
delay is also active at power on of the system
.
F
0
20
3
Min
1
C3
Time delay for compressor3 restart
E.g. If this parameter is set at 3MIN,then
after cutting off the compressor3 at set
temperature compressor3 will not
Restart for a minimum of 3min.This time
delay is also active at power on of the system
.
F
0
20
3
Min
1
C4
Time delay between any two compressors
start.
F
0
120
10
Sec
1