Troubleshooting Guides
8-21
#3758412 - Revision B - December, 2006
EVAPORATOR TEMPERATURE / SEALED SYSTEM LOW-SIDE PRESSURE CORRELATION
Pressure
10” Vac / -.69 Bar
7” Vac / -.48 Bar
4” Vac / -.28 Bar
0” Vac / 0 Bar
2 Psi / .14 Bar
4 Psi / .28 Bar
7 Psi / .48 Bar
9 Psi / .62 Bar
12 Psi / .83 Bar
15 Psi / 1.03 Bar
18 Psi / 1.24 Bar
22 Psi / 1.51 Bar
26 Psi / 1.79 Bar
30 Psi / 2.07 Bar
35 Psi / 2.41 Bar
40 Psi / 2.76 Bar
45 Psi / 3.10 Bar
51 Psi / 3.52 Bar
57 Psi / 3.93 Bar
64 Psi / 4.41 Bar
71 Psi / 4.90 Bar
78 Psi / 5.38 Bar
Temperature
-30°F / -34°C
-25°F / -32°C
-20°F / -29°C
-15°F / -26°C
-10°F / -23°C
-5°F / -21°C
0°F / -18°C
5°F / -15°C
10°F / -12°C
15°F / -9°C
20°F / -7°C
25°F / -4°C
30°F / -1°C
35°F / 2°C
40°F / 4°C
45°F / 7°C
50°F / 10°C
55°F / 13°C
60°F / 16°C
65°F / 18°C
70°F / 21°C
75°F / 24°C
NOTE:
The temperature/pressure table at
right is for reference only. A unit's tempera-
ture/pressure correlation may differ from
those listed due to: variations in evaporator
thermistor location, set-points, where the
sealed system is in the refrigeration cycle,
etc.
If a unit is experiencing temperature prob-
lems, it is recommended that you follow the
"Pointers" in the first column of the General
Troubleshooting Guide. After all mechanical
and electrical components have been ruled
out, sealed system pressures can be
checked by applying solder-on process
valves and referencing the preceding page.
Do NOT use bolt-on process valves as they
are prone to leak.
This table should only be used as a last
quick check before entering the sealed sys-
tem.
PRESSURE INDICATIONS
If low-side pressure is
NORMAL
LOW
LOW
HIGH
HIGH
& high-side pressure is
NORMAL
LOW
HIGH
LOW
HIGH
possible problem is
MECHANICAL
(see General Troubleshooting Guide)
LEAK
RESTRICTION
INEFFICIENT COMPRESSOR
OVER CHARGE