(©January, 2008)
Air Technology Systems, Inc.
BNB Ultrasonic Humidifier Installation, Operation & Maintenance Manual
2-1
2.0
INSTALLATION
2.1
Receiving the Equipment
Your Ultrasonic humidifier has been tested and inspected prior to shipment. To ensure that your equipment has
been received in excellent condition, make a visual inspection of the equipment immediately upon delivery. Care-
fully remove the shipping container and all protective packaging. Open the box and thoroughly inspect the unit for
any signs of transit-incurred damage. If there is shipping damage, it must be noted on the freight carrier's delivery
forms
BEFORE
signing for the equipment. Any freight claims
MUST
be done through the freight carrier. SATS
ships all equipment FOB factory. SATS is not liable for any equipment damage while in transit. SATS can assist in
the claim filing process with the freight carrier. Should any such damage be present, notify the SATS Product
Support Group prior to attempting any repairs. Refer to Section 6.0 of this manual for instructions.
Check the equipment against the packing slip to see if the shipment is complete. Report all discrepancies to the
appropriate authority.
Contents of Package:
1. Humidifier
2. Main Power Cable (2-conductor or 4-conductor with connector; 79" long).
3. Control Cable (4-conductor with connector; 79" long).
4. Installation, Operation and Maintenance manual.
Avoid dropping or jarring the unit to prevent damage to the internal parts. The unit should always be stored in a dry
location prior to installation.
A Data Package has been sent with your unit. It contains this manual, system drawings, applicable MSDS’s and
other applicable instructions based on the configuration and options of your unit. The data package has been
placed in your unit in a clear plastic envelope. These documents need to be kept with the unit for future reference.
2.2
Site Preparation
SATS ultrasonic humidifiers are designed with easy service access in mind. Install the unit in a secure location
where it cannot be tampered with and the power switch cannot be inadvertently turned off. Allow access to the
unit for routine operation, servicing and for necessary maintenance. Position the humidifier in such a way that the
unit can be easily removed for future maintenance and inspection. Refer to the installation drawing provided with
your unit for the dimensions of the humidifier.
NOTE
Working clearance requirements need to be
established prior to mounting the unit. Refer
to local and national electrical codes.
When selecting the installation location,
attention should be paid to the air flow in the
room so that the atomized mist can be
uniformly diffused throughout the room. When
it is installed above the air conditioner, ensure
mist isn’t attracted toward the bottom of the
humidifier. If any obstacle exists in front of the
atomized mist outlet, the mist will be con-
densed on the obstacle to form water drop-
lets.
Figure 1- Installation of Humidifier