6. Technical data
6.1. Application limits
Operation limits
Operating Temperature
Min
-10 °C
Max
+ 40 °C
Air humidity range
0-90%
Nominal power supply
230 V / 1ph / 50-60 Hz
Voltage tolerance
± 10%
Frequency tolerance
± 2%
Storage limits
Temperature
Min
- 20 °C
Max
+ 50 °C
Humidity
Max
90%
INFORMATION
Other limits not specified in this table can be found in the rest of this manual
6.2. Technical data
NOTES ON TECHNICAL DATA:
* Operating at nominal fan speed
** Measured at 2m distance from unit, in a free field, unit operating at nominal conditions.
According to ISO 9614.
This information must be made known to all personnel operating this unit and in the proximity
thereof.
Model
Air Booster2
Nominal Airflow
m
3
/h
2880
Maximum Airflow
m
3
/h
5200
Power consumption*
kW
0,075
Operating current (OA)*
A
2
Maximum operating current (FLA)
A
2,2
Raised floor overpressure*
Pa
25
External sound pressure level**
dB(A)
64
Weight
kg
25
Height x Width x Depth
mm
598 x 598 x 260