STUDER Innotec
XP-COMPACT
XP-COMPACT V5.7
10/79
3
Mounting and installing
3.1 Installation place
The location of the XP-COMPACT must be driven by the following criteria:
−
Protection from unauthorized handling
−
Dry dust free room, no condensation
−
Never install directly over the battery and never in a cabinet together with the
batteries
−
Keep ventilation holes free
−
In mobile installations it is important to keep the vibrations down as low as
possible
3.2 Fixing
3.2.1 Fixing the XP-COMPACT
Basically the XP-COMPACT can be installed in any
desired location. Preferred is that the appliance be wall
mounted with battery cables downwards. The XP-
COMPACT is fixed on the wall with four screws through
the four holes (diameter 5.5mm) which are accessible from
the outside. In motor vehicles XP-COMPACT must be
fixed on vibrations reducing elements. The XP-COMPACT
must not be fixed on a combustible base, as the back of
the casing can get hot and reach up to 80 degree Celsius.
3.2.2 Protection cover IP-23
This cover IP23 (Order ref. CIP-23) can be easily
installed after the fixation of the XP-COMPACT. For that
release a little the too screws down and more the tow up.
Then it’s possible to pass the IP 23 cover between the
XP-COMPACT and the wall. The cover must touch the
screws. Lock on the four screws, it’s ready.
3.3 Connections
3.3.1 General instructions on connecting
−
The cable connection on the terminals AC INPUT / AC OUTPUT / 16A 230VAC
are carried out with a screwdriver Nr.1 and the connection on the SOLAR
terminal with a screwdriver Nr.2.
−
The conductor cross section on the terminals AC INPUT / AC OUTPUT / 16A
230VAC of the connecting cable must be minimum 2.5mm2.
−
All connecting cables and also the mounted battery cables, must be fixed with
strain relief clamps.
−
The XP-COMPACT is delivered with battery cables already connected.
−
The battery cables must never be extended. If the extension is unavoidable then
the conductor cross section must be elevated accordingly.
−
To protect the battery cable, a fuse corresponding to the conductor cross
section must be fixed directly on to the battery.
Содержание XP-COMPACT-XPC 1400-12
Страница 28: ...STUDER Innotec XP COMPACT XP COMPACT V5 7 28 79 8 Technical Data ...
Страница 34: ...STUDER Innotec XP COMPACT XP COMPACT V5 7 34 79 2 3 2 Serieschaltung 2 3 3 Parallel Serieschaltung ...
Страница 54: ...STUDER Innotec XP COMPACT XP COMPACT V5 7 54 79 8 Technische Daten ...
Страница 79: ...STUDER Innotec XP COMPACT XP COMPACT V5 7 79 79 8 Données techniques ...