Programming (possible only with the remote control RCC-01)
The XP-COMPACT (except for 60Hz versions) is equipped with a Flash
processor fitted out with EEPROM Memory, which means that even when it is
disconnected from the battery, the parameters that were programmed for the
application remain after a new connection to the battery.
It is possible to reinitialize (RESET) the XP-COMPACT by pressing
simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A
beep will confirm the RESET. The inverter switches off after this operation. It
can be turned on again after the beep. The programmed parameters will
remain.
5.1 Standard
setting
The XP-COMPACT is delivered with the following default settings:
Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13
Battery voltage :
Low voltage
11.6V / 23.2V / 46.4V
Float Charge
13.5V / 27.0V / 54.0V
End of Charge Voltage 14.4V / 28.8V / 57.6V
Equalization
15.6V / 31.2V / 62.4V
Absorption Time :
2 Hours
Equalizing Time :
20 Minutes
5.2 Reset value (default settings)
To come back to the default settings, press simultaneously on the push buttons
20/21 during at least 2 seconds. A beep will confirm the comeback to the factory
settings. The inverter switches off after this operation. It can be turned on again after
the beep.
5.3 Battery voltages and absorption time
5.3.1 Set the voltage and timing threshold
The programming is done in accordance with
the following steps:
Push and hold down, the Push Button 21
(Program) and the Push Button 19 (Change
status) for minimum 2 seconds
simultaneously.
With the Push Button 20 (select) select which
of the battery level and of the absorption time
have to be changed.
These four red LED’s show the function set:
Low voltage
LED 13 (ON/OFF)
Float charge
LED 12 (Batt. Low/high)
Absorption (End of charge)
LED 11 (Overload)
Equalization
LED 10 (Overtemp.)
Absorption Time
LED 10/11/12/13 (altogether)