Note: In the Inverter operation, The COMPACT generates a true sinusoidal and quartz stabilized 
output voltage. When, however the COMPACT is supplied from a grid or a generator and the  
transfer contact is active, then you have at the output AC OUT the same voltage as that at the 
input. This voltage can not be modified by the COMPACT! 

4.7.1  Set the transfer voltage threshold 

The voltage threshold of the transfer can by adjust between 150 to 230V with the turning knobs 
(23). From factory this value is 200V. Majority’s of appliances can working on this voltage. When 
the Input voltages reach the settled value on turning knob, the inverter switch off and the AC 
INPUT go directly on the AC OUTPUT. When the voltage INPUT is less of 20V the value set, the 
transfer is stop and the OUTPUT switch back on the inverter.  
 

Don’t use the turning knobs “TRANSFERT” (23) to adjust the AC OUTPUT voltage! 

This is only it’s only a voltage threshold level to enable or disable the transfer. 

4.7.2  FAST (UPS)- MODE for the Transfer Switch 

The quick and break free Transfer mode is programmed with a slide switch „Transfer Delay“ OFF, 
which is on the front side (cable connections side). 
The aim of the COMPACT is to supply the consuming device with a break-free alternating voltage. 
When the incoming voltage AC IN no longer matches values which have been set with the Turning 
Knob 23, the Inverter switches on at once. The transfer is carried out in 0.02 seconds. This quick 
transfer ensure a break-free function for most consuming devices . If you have an alternating 
voltage back at the input AC IN, transfer system starts up again without any break, and the inverter 
is stopped.  

4.7.3  Delayed mode of the Transfer System 

The delayed mode of the transfer system „Transfer Delay ON“ is programmed with the slide switch 
on front with the cable connections. The COMPACT provides a break-free alternating voltage for 
the consuming device. A quick transfer switch is not always sensible nor is it always desired.  For 
example, when the consuming devices are operated by a small back-up generator. An overload of 
a short duration on such  a generator, i.e. start of a vacuum cleaner etc., has the effect of 
decreasing the voltage for a short time. As in such cases the transfer to the Inverter is not 
desirable, the transfer system can be programmed with a delay. When the slide switch (Transfer 
delay) is  in the „On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If 
the voltage falls below 100Vac, the transfer takes place without delay! The transfer switching to the 
Inverter takes place without any break. 

4.8  The Solar charge regulator (option) 

The COMPACT also has a Solar Charge Regulator built in. For charging the batteries, Solar 
modules can be connected to the screw terminal SOLAR +/-. The in-built regulator is a „Shunt 
regulator“ for the maximum input current of 30A for C1312 and C2324 and 20A for C3548. The 
operating voltage of  Solar panels to be connected must match the actual operating voltage of the 
COMPACT and never exceeds the max. rated value. 

 

Under no circumstances should any other systems such as wind-generator be connected at 

the input of the Solar Charge Regulator

The Solar Charge Regulator works automatically and is always in operation. As soon as the energy 
is delivered from the Solar Charge Regulator, LED 3 “SOLAR CHARGE” is lit and the batteries are 
being charged. The Solar Charge Regulator works even when the Battery Charger is functioning. 
The way of working is the principally the same as that of the Battery Charger. The function is 
described in the section on Battery Charger. The programming and the adjustments are carried out 
in accordance with the same conditions. Check with your battery supplier which adjustments must 
be carried out for your battery.  

4.9 The Multifunctional Contact 

In the COMPACT there is a built-in programmable power relay. The potential-free change-over 
contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT.

 

Содержание C1312 COMPACT

Страница 1: ... C1312 COMPACT C2324 COMPACT C2324 COMPACT C2324 COMPACT C2324 COMPACT C3548 COMPACT C3548 COMPACT C3548 COMPACT C3548 Temperature sensor CT 35 Remote control RC 01 Solar charge regulator Cxxxx S Remote power sharing RPS 01 AC cable cover CFC 01 IP 23 top cover CxxxxIP23 STUDER INNOTEC TEL 41 0 27 205 60 80 Rue des Casernes 57 FAX 41 0 27 205 60 88 CH 1950 SION info studer inno com ...

Страница 2: ...connections 9 3 4 CONNECTING PLAN FRONT SIDE 9 3 5 CABLING WIRING 10 3 5 1 Pre installation settings 10 3 5 2 Connection to battery 10 3 5 3 Connection the 230Vac Consumer Device AC OUTPUT 10 3 5 4 Connection the 230Vac Input AC INPUT 10 3 5 5 Connect the Solarmodules SOLAR Only for solar option 11 3 5 6 Connection to Auxiliary Contact 11 3 5 7 Connection to Remote control 11 3 5 8 Connection to T...

Страница 3: ...ge 19 5 1 3 Auxiliary contact 19 5 2 RESET VALUE 19 5 3 BATTERY VOLTAGES AND ABSORPTION TIME 19 5 3 1 Table of voltage and timing threshold 19 5 3 2 Set the voltage and timing threshold 20 5 4 PROGRAM THE AUXILIARY CONTACT 20 5 4 1 Principle 20 5 4 2 The programming of the Auxiliary Contact is carried out in the following Steps 20 5 4 3 Example 21 5 4 4 Manual operating of Auxiliary Contact 21 5 5...

Страница 4: ...is 2 Years 1 3 Warranty Disclaimer We do not accept any responsibility for any damages occurring through use manipulation working situation and handling which are not explicitly mentioned in these operating instructions Following cases are not covered by the warranty High voltage at INPUT i e 48V at the Battery INPUT of COMPACT 1312 Reverse polarity on Battery connections reversed Running liquid o...

Страница 5: ...y other wet conditions The COMPACT may only be connected to lead acid or lead gel batteries Caution In normal use lead acid and lead gel batteries give out explosive gases Never smoke or allow a spark or flame in the vicinity of batteries The batteries must always be stored or placed in a well ventilated area they should be placed in such a way that there is no danger of short circuiting through c...

Страница 6: ...e a stand by emergency generator or the AC network With the transfer system on one side you have an alternating voltage at the output for use by the connected consumer devices On the other side the batteries are charged The distribution of energy between the consumer devices and battery charger is automatic 2 2 3 The Battery charger The built in battery charger is so arranged that it can charge th...

Страница 7: ...ected to COMPACT All operating elements and displays with the exception of the level adjustment are available on the remote control The remote control is furnished with a 20m long cable This cable can go to 40m long On the remote control output power and charging current are also shown 2 3 Battery connections Lead acid batteries are normally available in blocks of 2V 6V or 12V In most cases to gen...

Страница 8: ...he fixation of the COMPACT For that s release a little the too screws down and more the tow up Then it s possible to pass the IP 23 cover between the COMPACT and the wall The cover must touch the screws Lock on the four screws it s ready 3 3 Connection 3 3 1 General instructions on connecting The cable connection on the terminals AC INPUT AC OUTPUT 15A 230VAC are carried out with a screwdriver Nr ...

Страница 9: ...r delay Auxiliary Contact PE N L PE Remote Power sharing C 2324 Ubat Pnom 2300 VA Uin 150 250 Vac N Uout 230 V 50 Hz T y p 22 32 Vdc I Solar I Charge 70A 30A max O M A L B C D E F G H J K N A Battery Battery cable already installed B SOLAR Connecting terminal for Solar modules C Remote contr Connecting terminal for Remote Control RCC 01 D Equalize Slide switch for equalization of the Battery E Tra...

Страница 10: ... is produced because for a short time high current flows in the COMPACT to charge the capacitors For this reason follow strictly the safety measures described in this manual Check if the red LED OFF 13 is lit If it is not lit press shortly on the switch ON OFF 19 now OFF should be lit On connecting the battery the COMPACT needs 1 2 Minutes to calculate the actual capacity of the battery During thi...

Страница 11: ...The schematic view of the connections on the front show the relay in the non active mode 3 5 7 Connection to Remote control The Remote Control RCC 01 is connected in the terminal marked Remote control with a RJ11 8 connector The Remote Control can be plugged IN or plugged OUT during any operation situation Push in the connector without forcing it until you hear the click now the connector is locke...

Страница 12: ...0 Contact active Program STANDBY CHARGER Charger Invert er Program Change status Lock select CHARGER INVERTER RESET ALARM TRANSFER EQUALIZE 230V 25 1 3 4 5 21 6 2 14 23 22 24 7 8 20 10 11 12 13 19 15 16 17 18 9 Inverter output power 5 10 20 40 60 80 100 130 160 200 10 20 30 40 50 60 70 Charge current POWER MONITOR A 16A 0 INPUT LIMIT 26 4 Operating 4 1 Display and operating control elements ...

Страница 13: ...load or short circuit 12 Batt Low High Battery voltage is too low Battery voltage is too high 13 OFF COMPACT is turned off Turning it back on is only possible manually COMPACT is for the time being turned off Turning it back on will follow automatically 14 Battery Charger and or Solar Charge Regulator are doing an equalization cycle 15 18 Charge condition of Battery LED 15 Absorbtion time is runni...

Страница 14: ...d four times one after another in a short time then it no longer switches on automatically The LED 13 remains lit Press the push button 19 ON OFF in order to switch on the Inverter 4 5 3 Overheating Over Temp If the Inverter has been overloaded for a long time or it has been working in a to high surrounding temperatures it will switch off The LED 10 Over Temp is lit and the LED 13 OFF blinks After...

Страница 15: ...zation charge you must confirm with your supplier that the batteries are suitable for this process Equalization is recommended for the lead acid batteries in order to mix well the electrolyte fluid and to clean the lead plates Equalization mode should never be used when using Gel Batteries If the COMPACT is operating with a lead acid battery which is suitable for equalization the slide switch Equa...

Страница 16: ... developed algorithm calculates the actual state of charge of the battery and displays it on LED 15 18 The LED 14 is lit when the system is carrying out a charge cycle with equalization For safety reasons you must get the recommended charge voltage and charge currents from your battery supplier The voltage levels and charge characteristics can be changed through Programming The instruction for pro...

Страница 17: ...eak free alternating voltage for the consuming device A quick transfer switch is not always sensible nor is it always desired For example when the consuming devices are operated by a small back up generator An overload of a short duration on such a generator i e start of a vacuum cleaner etc has the effect of decreasing the voltage for a short time As in such cases the transfer to the Inverter is ...

Страница 18: ... Control is supplied with a 20m long cable It can lengthened to 40m The Remote Control is suitable for surface mounting on the wall or on to a switch board It is fixed with 4 screws The COMPACT can also be programmed with the Remote Control The Programming is described in the section Programming The output power and the charging currents are displayed on the Remote Control In the Remote Control th...

Страница 19: ... is to be connected to a battery or after an interruption RESET it is always programmed with these standard settings In order to get to these settings during operation you must press the three Push Buttons 20 21 22 simultaneously for a minimum of 2 seconds 5 3 Battery voltages and absorption time The voltage levels low voltage float charge end of charge and equalization and the duration of the abs...

Страница 20: ...h your battery supplier 5 4 Program the auxiliary contact 5 4 1 Principle The Auxiliary Contact can be basically programmed for any operating situation of the COMPACT which is indicated with a LED The programming is possible for one or more operating situations If the contact is programmed for many situations it is activated as soon as the COMPACT finds itself in any one of the programmed situatio...

Страница 21: ... the light intensity To function as a twilight switch the Auxiliary Contact must be programmed so that the condition SOLAR CHARGE LED 3 is active Programming must be carried out in steps and in accordance with the description for the programming of the Auxiliary Contact 5 4 4 Manual operating of Auxiliary Contact 5 5 The Auxiliary Contact can be operated at any time with the Push Button 21 AUX CON...

Страница 22: ...erter will work continuously even if there is a correct AC voltage at the input CHARGER INVERTER AC OUT AC IN 1 2 7 8 9 Inverter and charger are both disabled Only the transfer switch function is enabled in input voltage and frequency is OK 6 Maintenance Apart from the periodic controls mentioned for the connections the COMPACT does not need any maintenance Keep the appliance clean and from time t...

Страница 23: ...ac Frequency range 44 65Hz Power factor correction PFC EN 61000 3 2 EN 61000 3 2 Solar Charge Regulator Floating Maximum no load voltage 25V 45V 90V Maximum charging current 30A 30A 20A Function principle Shunt regulator I U Uo equalize Battery Monitoring 25 C in accordance with TLBM True Level Battery Management Absorption charge time 0 4h End of charge cycle voltage 14 4V 28 8V 57 6V Floating vo...

Отзывы: