PROCESS CONTROL DIAGRAM
PAGE 21
PERIOD
Pre-vent.
Safety time
Operating
Post-ventilation
TIME INTERVAL
60 (10) seconds
15 seconds
heating time
120 seconds
CONTROL PANEL
Main Switch/clock
Operating lamp
Defect light
AUTOMATIC BOX
Low voltage relay
Thermostat
Photocell
Safety thermostat
Timer
FUNCTION
Circ.pump/relay
Fan/oil pump motor
Ignition
Pre-heating
Magnetic valve/oil pump
PROCESS
Ventilation
Combustion
Note: When starting first time the pre-ventilation time is 60 seconds.
When starting during the operating period the pre-ventilation time is 10
seconds
: Signal for either connection or disconnection
: Connection
: Disconnection
Please note: THE HEATER MUST NOT BE USED IN GARAGES, SERVICE STATIONS, OR OTHER
LOCATIONS WHEREVER THE USE OF OPEN FIRE IS PROHIBITED!