S-CB
+
Boiler Range Manual
70
Menu B: Hot water
B 5
L e g i o
t e m p
8 5
° C
Pasteurisation function of the boiler. This parameter is the
selected hot water temperature during the pasteurisation
function of the boiler.
Menu B: Hot water
B 6
L e g i o h y s t
2
° C
Pasteurisation function of the boiler. This parameter is the
selected hysteresis during the pasteurisation function of the
boiler.
Menu B: Hot water
B 7
L e g i o h o l d
2 M i n
Pasteurisation function of the boiler. This parameter is the
selected time period for the pasteurisation function of the
boiler.
Menu B: Hot water
B 8
L e g i o
i n t r
0
Pasteurisation function of the boiler. This parameter controls
if the CH demand can be interrupted by the pasteurisation
function of the boiler.
0 = Yes
1 = No
Menu B: Hot water
B 9
D H d s c O f f 2
4
° C
Function for the direct hot water boiler.
This parameter is de off set of the selected HW temperature
of the boiler.
Menu B: Hot water
B A
D H d s c P r b 2 3
2 0
° C
Function for the direct hot water boiler.
This parameter is the proportional range of the selected HW
temperature of the boiler.
Menu B: Hot water
B B
D H d s c D i f 2
1 0 ° C
Function for the direct hot water boiler.
This parameter is the hysteresis of the selected HW tem-
perature of the boiler.
Содержание S-CB+ Series
Страница 2: ......
Страница 3: ......
Страница 22: ...S CB Boiler Range Manual 22 ...
Страница 39: ...S CB Boiler Range Manual 39 9 4Electrical schematics ...
Страница 124: ...S CB Boiler Range Manual 124 ...