S-CB
+
Boiler Range Manual
112
Display message
C a s c a d e
B l o c k
9 9 9 , 5
h r s
Reason
One of the boilers of the cascade is in a lock-out.
Cause:
The unit is programmed in such a way that none of the boilers in a cascade will fire, if one
has a lockout. One unit has a lockout and therefore the whole cascade is blocked.
Corrective action:
Troubleshoot the fault of the unit in lock-out.
16.3 Maintenance attention function
The display shows alternately the base screen and this message, while backlight is blink-
ing.
The boiler is operating, but will count the exceeding hours.
A parameter must be changed, after service, to remove this message.
Display message
N e e d s
M a i n t e n a n
0 . 0
I g n i
t
i o n
c y c l e s
h r s
Reason
Maintenance option of total amount of ignition cycles has been
reached.
Display message
N e e d s
M a i n t e n a n
0 . 0
D a t e
h r s
Reason
Maintenance option of the date has been reached.
Display message
N e e d s
M a i n t e n a n
0 . 0
B u r n i n g
h o u r s
h r s
Reason
Maintenance option of total amount of burning hours has been
reached.
Display message
N e e d s
M a i n t e n a n
0 . 0
A l
l
h r s
Reason
One of the abovementioned maintenance options has been
reached.
This function/message is standard not activated, but can be acti-
vated/set by a trained engineer. This function does not overrule
the need for annual maintenance. The end user is always re-
sponsible for arranging annual maintenance.