31
14.6
Inputs and Outputs
The following tables shows the list of the inputs and outputs on the main controller of the heat pump with the ex-
pected settings. Some inputs and outputs can be configured in a different way onsite to manage other plant compo-
nents which are not within the heat pump casing
– these are marked by “x” under the available for the user.
14.6.1
M
AIN
C
ONTROLLER
-
I
NPUTS
ID
Use
Description
Features
Available for
the User
Inp
u
ts
BX1
B71
Plant heat exchanger inlet temperature
Temperature sensor NTC 10K
BX2
B85
Compressor inlet temperature
Temperature sensor NTC 10K
BX3
B3
Domestic hot water tank temperature
Temperature sensor NTC 10K
x
BX4
B4
Plant tank temperature
Temperature sensor NTC 10K
x
BX7
B9
Outdoor air temperature
Temperature sensor NTC 1K
BX8
B81
Compressor 1 outlet temperature
Temperature sensor NTC 10K
BX9
B82
Compressor 2 outlet temperature
Temperature sensor NTC 10K
BX10
B6
N/A
N/A
BX11
B1
Circuit 1 flow temperature
Temperature sensor NTC 10K
x
BX12
B21
Plant heat exchanger outlet temperature
Temperature sensor NTC 10K
BX13
B91
Source heat exchanger inlet temperature
Temperature sensor NTC 10K
BX14
B84
Liquid line temperature
Temperature sensor NTC 10K
H1
VK1
Heating request
Voltage free digital input; Or
0-10 Vdc input
x
H3
H82
Compressor inlet pressure
0-10 Vdc input
EX1
-
-
230 Vac digital input
x
EX2
E10
High pressure switch
230 Vac digital input
EX3
-
-
230 Vac digital input
x
EX4
E24
Plant flow switch / Plant pump thermal
protection
230 Vac digital input
EX5
E25
Soft starter compressor 1
230 Vac digital input
EX6
E27
Soft starter compressor 2
230 Vac digital input
EX7
E20
Phase sequence controller
230 Vac digital input
EX9
E5
Low tariff
230 Vac digital input
x
EX10
E6
Electrical power supply lock
230 Vac digital input
x
EX11
E14
Source pump thermal protection
230 Vac digital input
14.6.2
M
AIN
C
ONTROLLER
-
O
UTPUTS
ID
Use
Description
Features
Available for
the User
O
u
tp
u
ts
QX1
K1
Compressor 1
2 A - 230 Vac
QX2
K2
Compressor 2
2 A - 230 Vac
QX3
Q3
Domestic hot water 3 way valve
2 A - 230 Vac
x
ZX4
Q5
N/A
2 A - 230 Vac
QX5
Q9
Plant pump
2 A - 230 Vac
QX6
K40
Compressor carter electrical heaters
2 A - 230 Vac
QX7
-
-
2 A - 230 Vac
x
QX8
Q4
DHW Secondary Circulation Pump
2 A - 230 Vac
x
QX9
K10
Heat Pump Fault (Lock Out) Indication
2 A - 230 Vac
x
QX10
K42
Heat Pump Running (In Heating) Indication
2 A - 230 Vac
x
QX11
K44
Heat Pump Running (In DHW) Indication
2 A - 230 Vac
x
QX12
Y22
Reversing cycle valve
2 A - 230 Vac
QX13
K41
Electrical heater condensate tray
2 A - 230 Vac
UX1
V81
Expansion valve (positioner)
0-10 Vdc
UX2
K19
Modulating fan
0-10 Vdc
Содержание S-ASX 100