22
This graph is refered to the unit operating with a temperature at 10c (Density 1000 kg/m3)
Example - S-ASX 80 at 45c flow temperature at 7c air temperature:
-
Flow rate = 13620 l/h
-
Pump head available = Approx. 215 kPa
-
Pressure drop through DHW 3 port valve = Approx. 6 kPa
-
Total available head for system at 13,620 l/h = Approx. 209 kPa
9.2
Operating Limits
– Delta T
The below graph shows the operating area with the heat pump working within its limits.