TECHNICAL DATA

 

 
 

BOILER MODEL  

 

 

C3 C4  C5 C6 C7 C8 C9 

Number Of Sections 

 

3 4  5 6 7 8 9 

Input 

kW 

Btu/hr 

21.4 

73,017 

31.7 

108,160 

42 

143,304 

52.3 

178,448 

62.7 

213,932 

73.7 

251,464 

83.8 

285,926 

Output 

kW 

Btu/hr 

19.3 

65,852 

28.6 

97,583 

37.7 

128,632 

47.1 

160,705 

56.5 

192,778 

66.4 

226,557 

75.6 

257,947 

Water Content 

Lits 

10 12.5  15 17.5 20 22.5 25 

Maximum Working 
Pressure 

Bar 

Psi 

58 

58 

58 

58 

58 

58 

58 

Maximum Working 
Temperature 

°C 

90 90  90 90 90 90 90 

Flow Rate 10°C 
Differential 

Lt/sec 

M³/h 

0.47 
1.70 

0.71 
2.55 

0.95 
3.42 

1.10 
3.96 

1.40 
5.04 

1.60 
5.76 

1.90 
6.84 

Water Resistance 
10°C Differential 

mbar 

in Wg 

9.5 
3.7 

20 

7.8 

36.5 
14.4 

23 

9.1 

34 

13.4 

46 

18.1 

57 

22.6 

Gas Consumption 
Natural 

M³/h 

Ft³/h 

2.0 

70.21 

2.9 

104.00 

3.9 

137.79 

4.9 

171.58 

5.8 

205.70 

6.8 

241.79 

7.8 

274.93 

Gas Consumption 
LPG 

Kg/h 

Lbs/h 

1.54 
3.40 

2.29 
5.04 

3.03 
6.68 

3.77 
8.31 

4.52 
9.97 

5.31 

11.71 

6.04 

13.32 

Burner Pressure 
Natural 

mbar 

in Wg 

14.8 

5.8 

14.5 

5.7 

13.2 

5.2 

14.5 

5.7 

14.5 

5.7 

14.5 

5.7 

14.5 

5.7 

Supply Pressure 
Natural 

mbar 

in Wg 

18 

18 

18 

18 

18 

18 

18 

Burner Pressure 
LPG 

mbar 

in Wg 

31.8 
12.5 

30.8 
12.1 

30.3 
11.9 

29.7 
11.8 

29.4 
11.6 

29.1 
11.4 

31 

12.2 

Supply Pressure 
LPG 

mbar 

in Wg 

37 

14.5 

37 

14.5 

37 

14.5 

37 

14.5 

37 

14.5 

37 

14.5 

37 

14.5 

Main Injectors 
Natural 
LPG 

 

mm 
mm 

 

2.6 

1.75 

 

2.6 

1.75 

 

2.7 

1.75 

 

2.6 

1.75 

 

2.6 

1.75 

 

2.6 

1.75 

 

2.6 

1.65 

Shipping Weight 

Kg 

Lbs 

87 

192 

110 
243 

136 
300 

164 
362 

186 
410 

213 
470 

234 
516 

 
 

Geneva ‘PV’ as above with these changes. 
 

BOILER MODEL  ‘PV’

 

 

PV 3 

PV 4 

Maximum Working 
Pressure 

Bar 

Psi 

44 

44 

Expansion Vessel 
Capacity 

Lits 

Gal 

1.76 

10 

2.20 

Shipping Weight 

Kg 

Lbs 

94 

207 

118 
260 

 

 

TABLE. 1

 

Содержание Geneva C3

Страница 1: ...STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION OPERATING AND MAINTENANCE MANUAL ...

Страница 2: ... SECTION 5 FLUE SYSTEM SECTION 6 WATER CIRCULATION SYSTEM SECTION 7 ELECTRICAL SUPPLY SECTION 8 INSTALLATION SECTION 9 COMMISSIONING AND TESTING SECTION 10 SERVICING SECTION 11 FAULT FINDING FIGURE 1 CONTROL PANEL LAYOUT FIGURE 2 NOVA SIT 822 GAS VALVE FIGURE 3 ELEKTROGAS VM L GAS VALVE FIGURE 4 LPG CONVERSION ...

Страница 3: ...0 70 21 2 9 104 00 3 9 137 79 4 9 171 58 5 8 205 70 6 8 241 79 7 8 274 93 Gas Consumption LPG Kg h Lbs h 1 54 3 40 2 29 5 04 3 03 6 68 3 77 8 31 4 52 9 97 5 31 11 71 6 04 13 32 Burner Pressure Natural mbar in Wg 14 8 5 8 14 5 5 7 13 2 5 2 14 5 5 7 14 5 5 7 14 5 5 7 14 5 5 7 Supply Pressure Natural mbar in Wg 18 7 18 7 18 7 18 7 18 7 18 7 18 7 Burner Pressure LPG mbar in Wg 31 8 12 5 30 8 12 1 30 3...

Страница 4: ...P 342 Parts I and 2 BS 5440 parts 1 2 BS 5854 BS 6644 BS 6798 BS 6891 and British Gas Publications IM 11 Flues for Commercial and Industrial Gas Fired Boilers an Air Heaters The Gas Safety Installation and Use Regulations 1984 It is the law that all gas appliances are installed by CORGI registered contractors in accordance with the above regulations Failure to install appliances correctly could le...

Страница 5: ...1 BS 6644 where applicable The following notes are intended to give general guidance 5 2 The nominal flue size should not be less than that of the boiler flue connection and must be at least equivalent to a vertical height above the boiler outlet of 1 M 3 ft 3 in due allowance being made for any horizontal or inclined length and consideration being given to the position of the outlet The boiler fl...

Страница 6: ...ING DIAGRAM With Electronic Ignition Legend A ON OFF SWITCH I IGNITION ELECTRODE B1 LOCK OUT LAMP L CONTROL BOX B2 FLUE GAS SPILLAGE DETECTOR LIGHT N MAINS IN 230 VOLTS C FUSE 6 3 Amp O TIME SWITCH CONNECTIONS D FLUE SPILLAGE DETECTOR P PUMP INTERLOCKS PV MODELS E BOILER CONTROL THERMOSTAT Q ROOM THERMOSTAT WHERE FITTED F G BOILER LIMIT THERMOSTAT GAS VALVE R GAS DIFFERENTIAL PRESSURE SWITCH C 8 C...

Страница 7: ...de of the boiler should allow access of 500mm In addition a minimum clearance of 350mm should be available at the front of the boiler to enable servicing to be carried out 8 4 BOILER DIMENSIONS GENEVA C MODEL C 3 4 5 6 7 8 9 DIMENSIONS MM L 365 450 600 750 750 900 900 P 600 600 600 650 650 705 705 Ø A 1 1 1 1 1 4 1 1 4 1 1 4 1 1 4 Ø B 1 1 1 1 1 4 1 1 4 1 1 4 1 1 4 Ø C 1 2 1 2 1 2 1 2 1 2 1 1 G 135...

Страница 8: ...8 GENEVA PV MODEL PV 3 4 DIMENSIONS MM L 365 450 G 135 205 H 80 80 Ø I 130 130 M 40 40 CIRCULATING PUMP CHARACTERISTIC ...

Страница 9: ...ully Automatic Models see Fig 2 3 1 Connect pressure gauge to burner pressure test point 2 Switch on mains electrical supply 3 Turn ON main gas cock 4 Depress reset button on limit thermostat to ensure stat is made 5 Set control thermostat to required temperature and push button I on control panel to the ON position 6 After switching on ignition spark should appear followed by ignition of the main...

Страница 10: ...ling washers on manifold Replace if necessary 6 Re assembly is reversal of the above procedure 7 Check electrical connections to electrodes and electrodes for correct alignment 10 3 Test Soundness of Safety Shut Off Valve Proceed as detailed in 11 4 10 4 Re commission boiler as described in Section 10 11 0 FAULT FINDING 11 1 Fully Automatic Models 1 Boilers does not attempt to light Control box do...

Страница 11: ...k out a Faulty connections to main valve b Faulty main gas valve c Faulty control box 6 Noisy burner ignition a Improper distance between electrode and burner b Faulty electrical connection of the electrode c Low gas pressure at the burner 11 2 All Models 1 Presence of flue gases in the room a Flue size inadequate b Restriction in the flue 2 Presence of unburnt fuel in the room a Boiler needs clea...

Страница 12: ...eter Plus Boiler Pressure Gauge On PV Versions 4 Flue Gas Spillage Detector Light B2 5 Control Box Lock Out Light And Reset Button B1 6 Flue Gas Spillage Detector Reset E2 7 Boiler High Limit Thermostat Reset E1 Fig 2 NOVA SIT 822 GAS VALVE Inlet pressure test screw Burner pressure test screw Burner pressure regulator ...

Страница 13: ...crew clockwise the opening time can be slowed up to about 25 30 seconds NOTE Remove the red plastic cap to carry out following settings B Regulation of an Initial Quick Opening Interval Followed by a Slow Opening Interval The initial quick interval can be regulated from 0 to 100 of the whole valve movement by acting on the slow opening adjustment screw Valves are supplied with the screws completel...

Страница 14: ...tute the injectors on the main burner 5 Nova Sit 822 gas valve Remove the burner pressure regulator cover and screw the governor spring fully in replace the cover with blank supplied Elektrogas VM l gas valve Replace the governor spring with the one supplied 6 Test for soundness 7 Re commission boiler as described in section 11 Using LPG burner pressure as stated in Table 1 NOTE The gas supply pre...

Страница 15: ...15 ...

Страница 16: ...ny reserves the right to change the specification and dimensions without prior notice 6 96 STREBEL Ltd 1F Albany Park Industrial Estate Frimley Road Camberley Surrey GU15 2PL Telephone 01276 685422 Fax 01276 685405 ...

Отзывы: