ASSEMBLY INSTRUCTIONS FOR:
Page 8
11/07/00
Positioning the baffles
Push the Baffles into the flue–ways as far as the stop Fit
standard equipment in accordance with table below.
Flue gas temperature can be raised by removing the baffles.
Standard boilers are equipped with the following baffles.
Boiler
sections 4 5 6 7 8 9
2nd
Pass
6xA 6xA 6xA 6xA 6xA 6xB
3rd
Pass
6xB 6xB 4xB 4xB
With less than 6 baffles the lower passes remain free.
The flue gas temperature of a boiler depends on boiler water
temperature and boiler capacity. If boiler water temperature is
reduced the flue gas temperature is also reduced. If boiler
capacity is reduced by means of a different burner setting or by
the first stage of a two-stage burner, the flue gas temperature is
also reduced. The flue gas temperature rises by some 20ºC –
40ºC in the case of dirty flue-way surfaces, depending on the
degree of fouling.
Influence of baffles
If the baffles in the 3rd flue pass are removed, the flue gas
temperature rises by approx. 20ºC; if the baffles in the 2nd flue
pass are also removed, the flue gas temperature rises by a total
of approx. 40ºC.
NOTE:
RU 2s baffle details in Fig 8.2.
The RU 3s range of boilers do NOT use flue gas baffles.
Alternatively they have ribbed intermediate sections
denoted by the section legs painted in green.
Influence of water temperature
A change of 10ºC in the water temperature produces a change in
flue gas temperature of approx. 5ºC– 8ºC.
Boiler water and return temperatures
The boiler is operated with low flue-gas temperatures in order to
achieve maximum efficiency. If the boiler water or return
temperatures are too low, there is a danger that heating surfaces
will become fouled and encrusted this results in higher flue gas
temperatures, making boiler cleaning difficult, and in extreme
cases cause damage.
The following conditions must be maintained:
Oil fired:
boiler water temperature
min: 60ºC
Return
water
temperature min:
50ºC
Gas fired
boiler water temperature
min: 70ºC
Return
water
temperature min:
60ºC
RU 1s
max. kW
oil kg/h
Nat. gas
m /h
4
190
17.5
22
5
250
23
29
6
320
29.5
37
7
390
36
46
8
460
42
54
9
525
47.8
61
Type and
no. of sections
Output and fuel consumption
Refer to Fig. 7.2 for technical data on the RU 2s and
Fig. 6.3 for the RU 3s
Positioning the Baffles
ASSEMBLY
INSTRUCTIONS
FOR:
RU 1s Assembly
Содержание BRU 1 Series
Страница 16: ...ASSEMBLY INSTRUCTIONS FOR Page 16 11 07 00 ASSEMBLY INSTRUCTIONS FOR RU 1s Assembly ...
Страница 17: ...ASSEMBLY INSTRUCTIONS FOR Page 17 11 07 00 ASSEMBLY INSTRUCTIONS FOR RU 1s Assembly ...
Страница 23: ...ASSEMBLY INSTRUCTIONS FOR Page 23 11 07 00 ASSEMBLY INSTRUCTIONS FOR RU 2S BRU 2S RU 2s Assembly ...
Страница 29: ...ASSEMBLY INSTRUCTIONS FOR Page 29 11 07 00 ...