UPS (Uninterrupted Power Supply)
It is mandatory that the printer is powered through a UPS unit, provided by the customer.This ensures
that—
•
the quality of printing is not affected by power fluctuations from the mains.
•
the printer computers can perform a “graceful shutdown” in the event of a power failure.
The UPS specifications are listed below.
Output
Output Power Capacity
2100 W (minimum)
Nominal Output Voltage
230 VAC
Output Frequency (sync to mains)
50/60 Hz
±
3 Hz user adjustable
±
0.1
Topology
Double conversion online
Waveform type
Sine wave
AC output static voltage regulation
±
2%
Output Connections
IEC 320 C19
Batteries & Runtime
Bridging time
Minimum 60 minutes at 1500 W
Interface port(s)
RJ-45 Serial, Smart-Slot
Network Management Cards
Remote monitoring and control
Via the LAN network
Computer interface
Command line ability
1
Simultaneous remote management access
Via Telnet or SSH
Ability to configure time lag from power failure
10 minutes
Reliability
MTBF
36 months (minimum)
Table 4 UPS Requirements
2
____________________________________________________
1
Command line ability is necessary for the UPS to be able to execute script located in the printer software.
2
The UPS requirements are based on the time it might take to complete a "graceful system shutdown."
Objet1000 Plus
Electrical Requirements
15