background image

BT SERIES

THERMAL SHUT-OFF VALVES

WWW.BITORQ.COM

1

OPERATIONS AND MAINTENANCE MANUAL

Models FL-BT-149X

I. OVERVIEW OF THERMAL SHUT-OFF VALVES

BI-TORQ Valve Automation automatic thermal shut-off valves are designed for flow shutoff protection in piping systems 
handling flammable gasses or liquids, solvents, toxic fluids, or any other potentially dangerous media. These fire 
control valves terminate flow in the event of fire, aiding in reducing fire intensity. In the event of fire, the fusible link 
separates, allowing the top mounted spring pack to drive an API607 fire safe rated valve into a closed position. Fusible 
links are available in a range of temperature settings. The thermal shut-off valves also are available in a fail open 
position, ideal for a sprinkler system in the event of a fire.

The thermal shut-off valves  you have received has been assembled and tested at our factory with attention to safety 
in mind. BI-TORQ Valve Automation uses high quality materials and tested engineering to ensure that this product will 
operate safely and reliably. Carefully read all instructions before handling in order to avoid injury to the operator or 
damage to the product.

NOTE: Please refer to the attached assembly drawing FL-BT-0600 for parts identification and complete parts list.

II. GENERAL SAFETY INSTRUCTIONS

WARNING: THIS ASSEMBLY WAS SHIPPED FROM THE FACTORY IN THE UNARMED POSITION AND IS READY FOR INSTALLATION 
IN LINE. USE EXTREME CAUTION IN HANDLING THE ASSEMBLY BECAUSE THE SPRING PACK IS UNDER FULL TENSION. 

NOTE:THE VALVES ARE SHIPPED IN THE CLOSED POSITION.

The unit must be installed in a location with carefully maintained ambient temperatures. Installing the link 

 

in locations where high temperature fluctuations are possible (such as direct sunlight) is not recommended. Exposure to 
high ambient temperatures can cause the fusible links to break prematurely. (See chart 1 for link temperature ratings.)

9

10

12

11

8

16

15

14

ILLUSTRATION 1.1

 

all reference numbers

refer to drawing FL-BT-0600

Part Number

Yield Temp.

Max. Ambient Temp.

314135

135°F/57°F

104°F/41°C

314165

165°F/74°C

135°F/57°C

314212

212°F/100°C

185°F/82°F

314280

280°F/138°C

253°F/123°C

314360

360°F/182°C

330°F/166°C

Series

Links per assembly

FL-BT-149X

8

IMAGE OF FUSIBLE LINK

published 2/13/20

Отзывы: