Strahman Bi-Torq BT Series Скачать руководство пользователя страница 4

BT SERIES

THERMAL SHUT-OFF VALVES

WWW.BITORQ.COM

4

OPERATIONS AND MAINTENANCE MANUAL

Models FL-BT-149X

VI. OPERATING THE DECLUTCHABLE MANUAL OVERRIDE GEAR

IMPORTANT: Make sure that the fusible links have been removed before attempting to operate the valve with the 
declutchable manual override. 

Use the following instructions to 

ENGAGE

 the declutchable manual override.

1.  Using one hand, grab the override engagement handle, squeezing the bottom handle and top handle together.
2.  With the handles still squeezed together, rotate the handle from its declutched position upward toward the

 

spring pack mounting flange until the handle locking tabs are inline with their locking positions.

 

NOTE: In some cases the override gear teeth will not mesh correctly when rotating the handle upward. If this 
occurs, rotate the override handwheel slightly to mesh the gears and then rotate the declutch handle upward.

3.  Once the override handle is in its locked position, the override is ready to be used. Clockwise rotation of the 

override handwheel will produce clockwise rotation of the override output and valve. Conversely,

 

counterclockwise rotation of the handwheel will produce counterclockwise rotation of the override output,

 

and valve.

Use the following instructions to 

DISENGAGE

 the declutchable manual override.

 

Note: When the assembly is rearmed with the fusible links back in place, the the manual override must 
be returned to its declutched position. Reversing the procedure above will return the override to the declutched 
position. Make sure that the handle locking tabs are inserted into their locking position on the override housing. 

Leaving the declutch engaged will prohibit the spring return unit from cycling the valve to the closed position when the 
fusible links yield. Leaving the unit in the engaged position will prevent the unit from operating correctly, may cause 
damage to the override as well as drivers linkages, etc. and void the override warranty.

IMPORTANT: The fusible links will have to be reinstalled and the declutch disengaged before the assembly is properly 
armed.

The picture on the left shows the declutch operator in the disengaged 
to allow the spring pack to close the valve when the fusible links yield. 
As shown, the handle arrangement is pinned in the down position. The 
handwheel should rotate freely in either the clockwise or counterclockwise 
directions without affecting the valve rotation.

The picture on the left shows the declutch in the “override” position, or 
“engaged,” for operating the valve manually. As shown, the handle ar-
rangement is pinned in the up position for override. Rotation of the hand-
wheel clockwise will rotate valve clockwise (generally closed

 

direction); rotation of the handwheel counter-clockwise will rotate actua-
tor counterclockwise (generally open).

IMPORTANT: FUSIBLE LINKS MUST BE REMOVED BEFORE ATTEMPTING TO 
OPERATE THE VALVE WITH THE DECLUTCH.

DISENGAGED

ENGAGED