CLEARANCES TO COMBUSTIBLE MATERIAL
The clearances shown in this section have been determined by test according to procedures set out in
safety standards ULC S610 (Canada) and UL127 (U.S.A.). When the fireplace is installed so that its surfaces
are at or beyond the minimum clearances specified, combustible surfaces will not overheat under normal
and even abnormal operating conditions.
No part of the fireplace may be located closer to combustibles than the minimum clearance figures given.
The following clearances meet the minimum requirements for a safe installation.
Side wall
: 24" (61 cm) measured from the inside door frame.
Side mantle
: 5 5/8" (143 mm) (3" (76 mm) maximum of protrusion) measured from the inside door frame.
Wall in front of fireplace
: 48"
Ceiling
: 80" (2.03 m) measured from the base of the fireplace.
Fireplace enclosure
:
Back wall
: 0"
Sides
: 0"
Floor (under the fireplace)
: 0"
Chimney
: 2" (50 mm)
Combustible shelf
: 48" (122 cm) measured from the base of the fireplace for a shelf with a depth of 12" or
less.
7.1
Locating the Certification Label
Since the information given on the certification label
attached to the appliance always overrides the
information published in any other media (owner’s
manual, catalogues, flyers, magazines and/or web
sites), it is important to refer to it in order to have a
safe and compliant installation. In addition, you will
find information about your fireplace (model, serial
number, etc.). You can find the certification label
under the door, on the left hand side of the
fireplace.
Содержание Valcourt FP12 Mundo
Страница 11: ...FP12 Mundo Installation and Operation Manual 11 ...
Страница 39: ...FP12 Mundo Installation and Operation Manual 39 ...
Страница 59: ...FP12 Mundo Installation and Operation Manual 59 Direct installation Exterior offset installation ...
Страница 91: ...FP12 Mundo Installation and Operation Manual 91 APPENDIX 6 EXPLODED DIAGRAM AND PARTS LIST ...