44
FP12 Mundo - Installation and Operation Manual
6.3.2
Minimum Heart Extension Requirements
The hearth extension floor area must extend at least 18" (457 mm)* in front of the hearth
(A)
and at least
8" (203 mm) on each side of the door opening (
D
). The joint between the hearth extension and the fireplace
hearth needs to be made of non-combustible material such as sheet metal (not included).
* On a raised base installation of more than 4", a non-combustible hearth extension floor area must
extend at least 16" (406 mm) in front of the hearth.
CLEARANCES
A
18" (457 mm)*
B
41 1/2" (1054 mm)
C
8" (203 mm)
*On a raised base installation of more than 4", a non-combustible hearth extension floor area must
extend at least 16" (406 mm) in front of the hearth.
Содержание Valcourt FP12 Mundo
Страница 11: ...FP12 Mundo Installation and Operation Manual 11 ...
Страница 39: ...FP12 Mundo Installation and Operation Manual 39 ...
Страница 59: ...FP12 Mundo Installation and Operation Manual 59 Direct installation Exterior offset installation ...
Страница 91: ...FP12 Mundo Installation and Operation Manual 91 APPENDIX 6 EXPLODED DIAGRAM AND PARTS LIST ...