Third control level, (A parameters):
Setting of control parameters
Access to the third control level is granted when selecting the last P-parameter on the second
control level. Continue to press the UP key for approximately 10 seconds until “PA” appears.
Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the
first A-parameter of the third control level is indicated.
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will
give you the value of the respective parameter. By pressing the UP or DOWN key at the same time
the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by
simultaneously pressing the UP and DOWN key for approx. 4 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A1
Function of contact K1 at
sensor error
0: relay off
1: relay on
0
A2
Function of contact K2 at
sensor error
0: relay off
1: relay on
0
A3
Function of contact K3 at
sensor error
0: relay off
1: relay on
0
A4
Function of contact K4 at
sensor error
0: relay off
1: relay on
0
A5
Function of contact K5 at
sensor error
0: relay off
1: relay on
0
A6
Function of contact K6 at
sensor error
0: relay off
1: relay on
0
A10
Selection setpoint 2 or
DeltaW1
0: operation with setpoint 2
1: operation with deltaW1
1
A11
Selection setpoint 3 or
DeltaW2
0: operation with setpoint 3
1: operation with deltaW2
1
A12
Selection setpoint 4 or
DeltaW3
0: operation with setpoint 4
1: operation with deltaW3
1
A13
Selection setpoint 5 or
DeltaW4
0: operation with setpoint 5
1: operation with deltaW4
1
A14
Selection setpoint 6 or
DeltaW5
0: operation with setpoint 6
1: operation with deltaW5
1
A15
Display value
0: temperature display
1: pressure display
0
A16
Display mode
0: integrals
1: with decimals
1
A17
Alarm mode
0: Boundary alarm,
relative boundaries
1: Boundary alarm,
absolute boundaries
2: Range alarm,
relative boundaries
3: Range alarm,
absolute boundaries
0
A18
Special function at boundary
alarm
0: not activated
1: flashing display
0
A20
Minimum action time K1 “Off”
0...999 sec.
0 sec.
A21
Minimum action time K2 “Off”
0...999 sec.
0 sec.
Содержание ST710-PWHVM.26