4.2
Intrinsically safe inductive proximity switches
4.2.1
Dual module NAMUR sensors (44)
Applicable models
QN44_, QX44_
Specifications
Configuration
(2) NAMUR sensors (EN 60947-5-6)
Wire terminals for one or two solenoids
Operation
NO/NC (cam selectable)
Voltage range
5 -25 VDC
Current ratings
Target present
Target absent
Current < 1.0 mA (LED = OFF)
Current > 3.0 mA (LED = ON)
LED indication
Bottom sensor: green
Top sensor: red
Temperature range
-40° to 80° C
Operating life
Unlimited
Warranty
All mechanical parts
Two years
Sensor module
Five years
Use with intrinsically safe repeater barrier. NAMUR sensors conform to EN 60947-5-6 standard.
Touch & Tune switch setting
All adjustments assume you are looking down on the top of the
sensors. The edge of the cam metal strip will be at the edge of the
sensor target when activation occurs. When the cam is released be
sure it slides fully onto the spline. One spline tooth setting is 4 1/2°.
Valve closed to open in counterclockwise rotation (Fig. 1)
1. With the valve in the closed position, set the bottom cam so that
the metal activation strip is centered on the bottom sensor target
and the top cam is 180° from the bottom cam.
2. Lift up bottom cam and rotate counterclockwise until the green
LED is lit and remains lit when the cam is released, then rotate
clockwise until the green LED goes off and remains out when the
cam is released.
3. Move valve to the open position. Push down top cam and rotate
counterclockwise until the red LED goes off. Release cam.
Valve closed to open in clockwise rotation (Fig. 2)
1. With the valve in the closed position, set the bottom cam so that
the metal activation strip is centered on the bottom sensor target
and the top cam is 180° from the bottom cam.
2. Lift up bottom cam and rotate clockwise until the green LED
is lit and remains lit when the cam is released, then rotate
counterclockwise until the green LED goes off and remains out
when the cam is released.
3. Move valve to the open position. Push down top cam and rotate
clockwise until the red LED goes off. Release cam.
Notes:
1. With the valve in the closed position, the red LED is lit and the
bottom sensor is active (i.e. drawing less than 1.0 mA of current),
while the top sensor is inactive (i.e.. drawing greater than 3.0 mA
of current).
2. When the valve is in the open position, the green LED is lit and the
top sensor is active while the bottom sensor is inactive.
3. During valve transition from closed to open or open to closed
both LEDs will be lit and neither sensor will be active.
Bench test procedure
Use StoneL Light Read Tester or use a 24 VDC power supply. No series
load resistor required.
LED
LED
SOL +
SOL -
SOL PWR +
SOL PWR -
TOP SW +
TOP SW -
BTM SW +
BTM SW -
Models with 3 conduit entries have
an additional 2-pole terminal block
for second solenoid termination
SOL
PWR
2
1
SOL PWR +
SOL PWR -
SOL +
SOL -
Wiring diagram
Caution:
To prevent ignition of hazardous atmospheres,
replace cover before energizing the electrical circuits. Keep
cover tightly closed within operation.
Fig. 1 cam set for normally
open sensor function
Fig. 2 cam set for normally
closed sensor function
Reference controlled installation drawing #105193 for
proper intrinsic safety installation details. Find document
in the Appendix on page 49 or at
www.stonel.com/en/
products/quartz/installation-manuals
STOP